Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 5038551
Status: Active
Facility Name: Road Ranger #266
Address: 700 King Road
P.O. Box 408
New Berlin, IL 62670
County: Sangamon
Property Parcel:
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Y000765
Green Tag Issue Date: 6/12/2023
Green Tag Expiration Date: 12/31/2025

Owner Details

Owner Name: Road Ranger, LLC
Owner Address: 1501 Woodfield Rd., Suite 300 S
Schaumburg, IL 60173
Owner Status: Current Owner
Purchase Date: 10/4/2012
Type of Financial Responsibility: Self-Insurance
Financial Responsibility Reporting Due Date: 6/28/2025

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 4/3/2023 12/31/2025

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0033990 Road Ranger, LLC Current Owner 10/4/2012
U0028363 JEHC Development Inc. Former Owner 8/5/1999
U0034191 JEHL Development, Inc. Former Owner 1/1/1999

Permits (Unexpired)

Click for permit history
Permit Number Type Status OSFM Receive Date Issue Date Expiration Date Documents
00437-2025UPG Upgrade Approved / Issued 4/10/2025 4/11/2025 10/14/2025 Documents

Notice of Violations (Current)

NOV Number: E0020250694 (Pending)    Issue Date: 3/18/2025    Expiration Date: 5/17/2025    View NOV Form

Tanks Violation
Facility Farthest dispenser is greater than 40' and site lacks a communication system or system is inoperable

NOV Number: E0020251272 (Pending)    Issue Date: 5/15/2025    Expiration Date: 7/14/2025    View NOV Form

Tanks Violation
4 Tank interstitial sensors in alarm or failed test, must repair or replace.

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
12-1078 Eligible 12/6/2012 12/28/2012 $5,000
Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 12000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 11/22/1999 Abandoned Material:
Current Age: 25 Abandoned Date:
Install Date: 8/5/1999 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 8/5/1999

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Sacrificial Anode Flex Connector 10/22/2024 10/22/2027
Corrosion Prot - Piping Sacrificial Anode Flex Connector 10/22/2024 10/22/2027
Corrosion Prot - Piping Sacrificial Anode Flex Connector 10/22/2024 10/22/2027
Corrosion Prot - Piping Sacrificial Anode Flex Connector 10/22/2024 10/22/2027
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Composite Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 3/13/2025 3/13/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 450 with CSLD 3/13/2025 3/13/2026
Overfill Prev Device Overfill Drop Tube Valve 2/4/2025 2/4/2028
Piping Flexible Double Wall A.P.T. Poly Tech N/A N/A
Piping Flex Connector Steel N/A N/A
Piping Single Wall STP/Tanktop Sump 3/14/2025 3/14/2028
Leak Detect - Piping Sump Sensor 3/13/2025 3/13/2026
Spill Contain Device Single Wall Spill Bucket 10/22/2024 10/22/2027
Tank Composite Single Wall ACT 100 N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall A.P.T. Poly Tech Precision Test (Piping) Pass 3/13/2025



Tank Number 2

Capacity: 10000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 11/22/1999 Abandoned Material:
Current Age: 25 Abandoned Date:
Install Date: 8/5/1999 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 8/5/1999

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Sacrificial Anode Flex Connector 10/22/2024 10/22/2027
Corrosion Prot - Piping Sacrificial Anode Flex Connector 10/22/2024 10/22/2027
Corrosion Prot - Piping Sacrificial Anode Flex Connector 10/22/2024 10/22/2027
Corrosion Prot - Piping Sacrificial Anode Flex Connector 10/22/2024 10/22/2027
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Composite Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 3/11/2025 3/11/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 3/11/2025 3/11/2026
Overfill Prev Device Overfill Drop Tube Valve 5/9/2025 5/9/2028
Piping Flexible Double Wall A.P.T. Poly Tech N/A N/A
Piping Flex Connector Steel N/A N/A
Piping Single Wall STP/Tanktop Sump 10/22/2024 10/22/2027
Leak Detect - Piping Sump Sensor 3/11/2025 3/11/2026
Piping Single Wall Transition Sump 10/22/2024 10/22/2027
Leak Detect - Piping Sump Sensor 3/11/2025 3/11/2026
Spill Contain Device Double Wall Spill Bucket 5/9/2025 5/9/2028
Tank Composite Single Wall ACT 100 N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall A.P.T. Poly Tech Precision Test (Piping) Pass 3/13/2025
Tank Composite Single Wall ACT 100 Precision Test (Tank) Pass 2/4/2025
Leak Detect - Tank SIR and Prec Tightness Testing Warren Rogers Assoc. Petro Network S3 Version D Precision Test (Tank) Pass 12/17/2018



Tank Number 3

Capacity: 8000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 11/22/1999 Abandoned Material:
Current Age: 25 Abandoned Date:
Install Date: 8/5/1999 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 8/5/1999

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Sacrificial Anode Flex Connector 10/22/2024 10/22/2027
Corrosion Prot - Piping Sacrificial Anode Flex Connector 10/22/2024 10/22/2027
Corrosion Prot - Piping Sacrificial Anode Flex Connector 10/22/2024 10/22/2027
Corrosion Prot - Piping Sacrificial Anode Flex Connector 10/22/2024 10/22/2027
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Composite Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 3/13/2025 3/13/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 450 with CSLD 3/13/2025 3/13/2026
Overfill Prev Device Overfill Drop Tube Valve 5/9/2025 5/9/2028
Piping Flexible Double Wall A.P.T. Poly Tech N/A N/A
Piping Flex Connector Steel N/A N/A
Piping Single Wall STP/Tanktop Sump 10/22/2024 10/22/2027
Leak Detect - Piping Sump Sensor with positive shutdown 3/13/2025 3/13/2026
Spill Contain Device Double Wall Spill Bucket 5/9/2025 5/9/2028
Tank Composite Single Wall ACT 100 N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall A.P.T. Poly Tech Precision Test (Piping) Pass 3/13/2025
Tank Composite Single Wall ACT 100 Precision Test (Tank) Pass 3/13/2025



Tank Number 4

Capacity: 20000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 12/18/2012 Abandoned Material:
Current Age: 12 Abandoned Date:
Install Date: 10/18/2012 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 10/20/2012

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 3/11/2025 3/11/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 3/13/2025 3/13/2026
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 2/4/2025 3/13/2025
Overfill Prev Device Ball Float Vent Valve OPW 53VML 10/22/2024 10/22/2027
Overfill Prev Device Overfill Alarm 4/7/2023 4/7/2026
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Single Wall STP/Tanktop Sump 10/22/2024 10/22/2027
Leak Detect - Piping Non-Discriminating Sump Sensor with positive shutdown 12/8/2020 12/8/2021
Leak Detect - Piping Sump Sensor with positive shutdown 3/13/2025 3/13/2026
Piping Single Wall Transition Sump 10/22/2024 10/22/2027
Leak Detect - Piping Sump Sensor with positive shutdown 3/13/2025 3/13/2026
Spill Contain Device Single Wall Spill Bucket 10/22/2024 10/22/2027
Tank Fiberglass Double Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX Precision Test (Piping) Pass 3/13/2025
Tank Fiberglass Double Wall XERXES Precision Test (Tank) Pass 3/13/2025
Leak Detect - Tank SIR and Prec Tightness Testing Warren Rogers Assoc. Petro Network S3 Version D Precision Test (Tank) Pass 12/17/2019



Tank Number 5

Capacity: 20000 Petroleum Use:
Product: B-99 CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 12/18/2012 Abandoned Material:
Current Age: 12 Abandoned Date:
Install Date: 10/18/2012 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 10/20/2012

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping European with No Test Req Suction N/A N/A
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 3/13/2025 3/13/2026
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 5/15/2025 5/15/2026
Overfill Prev Device Overfill Alarm 4/7/2023 4/7/2026
Overfill Prev Device Overfill Drop Tube Valve 5/14/2025 5/14/2028
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Single Wall STP/Tanktop Sump 10/22/2024 10/22/2027
Leak Detect - Piping Sump Sensor with positive shutdown 3/13/2025 3/13/2026
Spill Contain Device Single Wall Spill Bucket 10/22/2024 10/22/2027
Tank Fiberglass Double Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX Precision Test (Piping) Pass 3/13/2025
Tank Fiberglass Double Wall XERXES Precision Test (Tank) Pass 3/13/2025
Leak Detect - Tank SIR and Prec Tightness Testing Warren Rogers Assoc. Petro Network S3 Version D Precision Test (Tank) Pass 12/8/2020



Tank Number 6

Capacity: 8000 Petroleum Use:
Product: Diesel Exhaust Fluid (Non-Regulated) CERCLA Substance:
Status: Unknown CAS Code:
Regulated Status: Non-Regulated Removed Date:
OSFM First Notify Date: 12/18/2012 Abandoned Material:
Current Age: 12 Abandoned Date:
Install Date: 10/18/2012 Red Tag Issue Date:
Last Used Date: Fee Due:
Product Date: 10/20/2012

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 17

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 10/22/2024 10/22/2027
Leak Detect - Piping Sump Sensor with positive shutdown 3/13/2025 3/13/2026



Name\ID 18

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 10/22/2024 10/22/2027
Leak Detect - Piping Sump Sensor with positive shutdown 3/13/2025 3/13/2026



Name\ID 19

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 10/22/2024 10/22/2027
Leak Detect - Piping Sump Sensor with positive shutdown 3/13/2025 3/13/2026



Name\ID 20

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 10/22/2024 10/22/2027
Leak Detect - Piping Sump Sensor with positive shutdown 3/13/2025 3/13/2026



Name\ID 20 Satelite

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 10/22/2024 10/22/2027
Leak Detect - Piping Sump Sensor with positive shutdown 3/13/2025 3/13/2026



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A

MFD Motorfuel Dispensing Forms