Division of Petroleum & Chemical Safety

 
Pay Tank Fees Online Print Detail Page Export to Excel

Facility Details

Facility Number: 5038551
Status: Active
Facility Name: Road Ranger #266
Address: 700 King Road
P.O. Box 408
New Berlin, IL 62670
County: Sangamon
Property Parcel:
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Y000765
Green Tag Issue Date: 6/12/2023
Green Tag Expiration Date: 12/31/2025

Owner Details

Owner Name: Road Ranger, LLC
Owner Address: 1501 Woodfield Rd., Suite 300 S
Schaumburg, IL 60173
Owner Status: Current Owner
Purchase Date: 10/4/2012
Type of Financial Responsibility: Self-Insurance
Financial Responsibility Reporting Due Date: 6/28/2025

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 4/3/2023 12/31/2025

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0033990 Road Ranger, LLC Current Owner 10/4/2012
U0028363 JEHC Development Inc. Former Owner 8/5/1999
U0034191 JEHL Development, Inc. Former Owner 1/1/1999

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violations (Current)

NOV Number: E0020250694 (Pending)    Issue Date: 3/18/2025    Expiration Date: 5/17/2025    View NOV Form

Tanks Violation
Facility Farthest dispenser is greater than 40' and site lacks a communication system or system is inoperable

NOV Number: E0020250695 (Pending)    Issue Date: 3/18/2025    Expiration Date: 5/17/2025    View NOV Form

Tanks Violation
2 Annual leak detection certification not completed (Required annually). - Expired 2/13/2025.
5 Drop tube valve or overfill alarm failed inspection. Repair or replace equipment. - Failed test2/4/2025.
2, 4 Line leak detection equipment in alarm or failed test, must repair or replace. - STP and UDC 18,19 and 20 satilite Sump sensors Failed test 2/4/2025.
1, 2, 3, 4, 5 Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry.
5 Tank interstitial sensors in alarm or failed test, must repair or replace. - Failed test 2/4/2025.
1, 3 Tank monitor does not appear to function properly and requires maintenance. - ATG does not print.
2, 3, 4, 5 Water in containment with required interstitial sensors - Remove water and repair containments to prevent water ingress.

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
12-1078 Eligible 12/6/2012 12/28/2012 $5,000
Pay Tank Fees Online

Tank Information

Tank Number Capacity Product Status Regulated Status Red Tag Issued Fee Due Abandon/Removal Date
1 12000 Gasoline - Regular Currently in use Federal $0.00
2 10000 Diesel Fuel Currently in use Federal $0.00
3 8000 Gasoline - Premium Currently in use Federal $0.00
4 20000 Diesel Fuel Currently in use Federal $0.00
5 20000 B-99 Currently in use Federal $0.00
6 8000 Diesel Exhaust Fluid (Non-Regulated) Unknown Non-Regulated

Dispenser Information

Name\ID Status
1/2 Active
3/4 Active
5/6 Active
7/8 Active
17 Active
18 Active
19 Active
20 Active
20 Satelite Active

MFD Motorfuel Dispensing Forms

No Forms Found