Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 5033172
Status: Active
Facility Name: AM PM Franklin, Inc. d/b/a Franklin Fast Stop
Address: 2930 Highway 104 Franklin, IL 62638
County: Morgan
Property Parcel: 14-36-207-019
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Y002310
Green Tag Issue Date: 8/21/2023
Green Tag Expiration Date: 12/31/2025

Owner Details

Owner Name: AM PM Franklin, Inc.
Owner Address: 2930 State Hwy. 104 Franklin, IL 62638
Owner Status: Current Owner
Purchase Date: 8/5/2020
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 1/27/2026

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 8/21/2023 12/31/2025

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0040039 AM PM Franklin, Inc. Current Owner 8/5/2020
U0013645 Prairieland FS, Inc. Former Owner 12/1/2013
U0004992 Lincoln Land FS, Inc. Former Owner 12/30/2010
U0032379 Flashes Junction, Inc. Former Owner 8/1/2002
U0008156 Junction Sales Inc. Former Owner 8/15/1994

Permits (Unexpired)

Click for permit history
Permit Number Type Status OSFM Receive Date Issue Date Expiration Date Documents
00927-2025CAT Cathodic Protection Cancelled by Contractor 7/17/2025 7/21/2025 1/21/2026 Documents

Notice of Violatlions (Current)

NOV Number: E0020251212 (Pending)    Issue Date: 5/8/2025    Expiration Date: 7/7/2025    View NOV Form

Tanks Violations
Facility Electrical Does Not Comply - Electrical connections on Tanks 2 and 3 are not sealed to prevent moisture.
2 Submit Notification Form for Product Change - Listed as Diesel but has Premium. It appears to have been this way for many years.
3 Verify and test piping sump sensor for positive shutdown - After fluid is removed test sensor.
1, 2, 3 Water in containment without required interstitial sensors - install cathodic protection on all exposed steel. - Water in transition sump. Remove water and prevent water egress or install Corrosion Protection.
3 Water in dispenser containment with interstitial sensors - Remove water and repair containments to prevent water ingress - Diesel fuel in the STP. Ivestigate and repair source.

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 10000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 11/2/1994 Abandoned Material:
Current Age: 31 Abandoned Date:
Install Date: 8/15/1994 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 8/15/1994

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 2/21/2025 2/21/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 2/21/2025 2/21/2026
Leak Detect - Tank Hydrostatic Reservoir Interstitial Monitoring Sensors 2/21/2025 2/21/2026
Overfill Prev Device Overfill Drop Tube Valve 6/20/2023 6/20/2026
Piping Flexible Double Wall Total Containment Enviroflex non-corrosive N/A N/A
Piping Flex Connector Steel N/A N/A
Piping Single Wall STP/Tanktop Sump 3/1/2023 3/1/2026
Leak Detect - Piping Sump Sensor 2/21/2025 2/21/2026
Piping Single Wall Transition Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A
Spill Contain Device Single Wall Spill Bucket 6/20/2023 6/20/2026
Tank Fiberglass Brine Filled Double Wall Containment Solutions N/A N/A
Vent, Riser, Fill Piping Steel risers N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall Total Containment Enviroflex non-corrosive Precision Test (Piping) Pass 2/21/2025



Tank Number 2

Capacity: 4000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 11/2/1994 Abandoned Material:
Current Age: 31 Abandoned Date:
Install Date: 8/15/1994 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 8/15/1994

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 2/21/2025 2/21/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 2/21/2025 2/21/2026
Leak Detect - Tank Hydrostatic Reservoir Interstitial Monitoring Sensors 2/21/2025 2/21/2026
Overfill Prev Device Overfill Drop Tube Valve 6/20/2023 6/20/2026
Piping Flexible Double Wall Total Containment Enviroflex non-corrosive N/A N/A
Piping Flex Connector Steel N/A N/A
Piping Single Wall STP/Tanktop Sump 7/12/2023 7/12/2026
Leak Detect - Piping Sump Sensor 2/21/2025 2/21/2026
Piping Single Wall Transition Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A
Spill Contain Device Single Wall Spill Bucket 6/20/2023 6/20/2026
Tank Fiberglass Brine Filled Double Wall Containment Solutions N/A N/A
Vent, Riser, Fill Piping Steel risers N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall Total Containment Enviroflex non-corrosive Precision Test (Piping) Pass 2/21/2025



Tank Number 3

Capacity: 4000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 11/2/1994 Abandoned Material:
Current Age: 31 Abandoned Date:
Install Date: 8/15/1994 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 8/15/1994

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 2/21/2025 2/21/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 2/21/2025 2/21/2026
Leak Detect - Tank Hydrostatic Reservoir Interstitial Monitoring Sensors 2/21/2025 2/21/2026
Overfill Prev Device Overfill Drop Tube Valve 6/20/2023 6/20/2026
Piping Flexible Double Wall Total Containment Enviroflex non-corrosive N/A N/A
Piping Flex Connector Steel N/A N/A
Piping Single Wall STP/Tanktop Sump 7/12/2023 7/12/2026
Leak Detect - Piping Sump Sensor 2/21/2025 2/21/2026
Piping Single Wall Transition Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A
Spill Contain Device Single Wall Spill Bucket 3/1/2023 3/1/2026
Tank Fiberglass Brine Filled Double Wall Containment Solutions N/A N/A
Vent, Riser, Fill Piping Steel risers N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall Total Containment Enviroflex non-corrosive Precision Test (Piping) Pass 2/21/2025
Tank Fiberglass Brine Filled Double Wall Containment Solutions Precision Test (Tank) Pass 4/3/2023

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A

MFD Motorfuel Dispensing Forms