Electrical Does Not Comply - Electrical connections on Tanks 2 and 3 are not sealed to prevent moisture. |
2 |
Submit Notification Form for Product Change - Listed as Diesel but has Premium. It appears to have been this way for many years. |
3 |
Verify and test piping sump sensor for positive shutdown - After fluid is removed test sensor. |
1, 2, 3 |
Water in containment without required interstitial sensors - install cathodic protection on all exposed steel. - Water in transition sump. Remove water and prevent water egress or install Corrosion Protection. |
3 |
Water in dispenser containment with interstitial sensors - Remove water and repair containments to prevent water ingress - Diesel fuel in the STP. Ivestigate and repair source. |