Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 5026672
Status: Active
Facility Name: Lincoln Prairie Behavioral Health Center
Address: 5230 S. 6th Street Road Springfield, IL 62703
County: Sangamon
Property Parcel: 22-27.0-126-001
Facility Type: Private Institution
Owner Type: Private
Green Tag Decal: Z004196
Green Tag Issue Date: 9/5/2024
Green Tag Expiration Date: 12/31/2026

Owner Details

Owner Name: Universal Health Services
Owner Address: 367 S. Gulph Road King of Prussia, PA 19406
Owner Status: Current Owner
Purchase Date:
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 1/29/2026

Motor Fuel Dispensing Permits

No MFD Permits Found

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0037805 Universal Health Services Current Owner
U0034992 Lincoln Prairie Behavioral Health Center Former Owner 5/1/2007
U0004159 Doctors Hospital Former Owner 5/1/2003

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violatlions (Current)

NOV Number: E0020252933 (Pending)    Issue Date: 11/4/2025    Expiration Date: 1/3/2026    View NOV Form

Tanks Violations
Facility Annual Emergency Stop Inspection not completed or inspection report not available.
3 Annual leak detection certification not completed (Required annually).
Facility Missing copies of Annual Walkthrough Inspection Report.
3 Overfill prevention equipment inspection(s) not completed (Required every 3 years).
3 Tank interstitial sensor functional test not accomplished (Required annually).
3 Triennial spill prevention equipment testing not completed.

IEMA Numbers Associated with the Facility

IEMA Number Inspection Date Inspection Type Permit Number
90-0965 5/1/1990 Removal Log 5114

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 2000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 5/1/1990
OSFM First Notify Date: 5/8/1990 Abandoned Material:
Current Age: 23 Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 2

Capacity: 1000 Petroleum Use: Back-up Generator
Product: Diesel Fuel CERCLA Substance:
Status: Condemned Tank CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 11/5/1992 Abandoned Material:
Current Age: 34 Abandoned Date:
Install Date: 5/17/1991 Red Tag Issue Date:
Last Used Date: 1/16/2023 Fee Due: $0.00
Product Date: 5/18/1991

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Sacrificial Anode Cathodic Protection 1/25/2021 1/25/2024
Corrosion Prot - Tank STIP3 Cathodic Protection with Dielectric Coating 1/25/2021 1/25/2024
Leak Detect - Piping European with No Test Req Suction N/A N/A
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 300c 2/21/2023 2/21/2024
Overfill Prev Device Overfill Drop Tube Valve 2/9/2022 2/9/2025
Piping Steel Single Wall Piping N/A N/A
Piping Not Installed STP/Tanktop Sump N/A N/A
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A
Spill Contain Device Single Wall Spill Bucket 2/9/2022 2/9/2025
Tank STIP3 Single Wall N/A N/A
Vent, Riser, Fill Piping Steel risers N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 3

Capacity: 4000 Petroleum Use: Back-up Generator
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 6/1/1994 Abandoned Material:
Current Age: 31 Abandoned Date:
Install Date: 4/22/1994 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 4/22/1994

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping European with No Test Req Suction N/A N/A
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 300c 11/7/2025 11/7/2026
Leak Detect - Tank Hydrostatic Reservoir Interstitial Monitoring Sensors 11/7/2025 11/7/2026
Overfill Prev Device Overfill Drop Tube Valve 11/7/2025 11/7/2028
Piping Flexible Double Wall Ameron FLX-3000 w/frp secondary N/A N/A
Piping Single Wall STP/Tanktop Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A
Spill Contain Device Single Wall Spill Bucket 11/7/2025 11/7/2028
Tank Fiberglass Double Wall Containment Solutions N/A N/A
Vent, Riser, Fill Piping Steel risers N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date

Dispenser Information



MFD Motorfuel Dispensing Forms

No Forms Found