Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 5021005
Status: Active
Facility Name: Logan Correctional Center
Address: 1096 1350th Street
Lincoln, IL 62656
County: Logan
Property Parcel:
Facility Type: State
Owner Type: State
Green Tag Decal: Z003899
Green Tag Issue Date: 4/3/2025
Green Tag Expiration Date: 12/31/2026

Owner Details

Owner Name: Illinois Department of Corrections
Owner Address: 1301 Concordia Court
P.O. Box 19277
Springfield, IL 62703
Owner Status: Current Owner
Purchase Date:
Type of Financial Responsibility: Self-Insurance
Financial Responsibility Reporting Due Date: 12/27/2025

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Fleet 7/27/2022 12/31/2024

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0007314 Illinois Department of Corrections Current Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violations (Current)

NOV Number: E0020250892 (Pending)    Issue Date: 4/3/2025    Expiration Date: 6/2/2025    View NOV Form

Tanks Violation
4, 5 Triennial testing for qualifying piping containment sump not completed (Required every 3 years). - STP tanktop sump failed testing requirements on 2/19/2025 and needs repaired and or replaced.

IEMA Numbers Associated with the Facility

IEMA Number Inspection Date Inspection Type Permit Number
N/A 4/2/2024 Abandonment Log 01162-2023ABN

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 3000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 10/1/1991
OSFM First Notify Date: 12/22/1987 Abandoned Material:
Current Age: 17 Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: 10/1/1991 Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 2

Capacity: 12000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 10/1/1991
OSFM First Notify Date: 12/22/1987 Abandoned Material:
Current Age: 31 Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: 10/1/1991 Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 3

Capacity: 2000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 5/9/1994
OSFM First Notify Date: 12/22/1987 Abandoned Material:
Current Age: 16 Abandoned Date:
Install Date: 1/1/1958 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 1/1/1978

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 4

Capacity: 4000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 4/30/1993 Abandoned Material:
Current Age: 33 Abandoned Date:
Install Date: 10/1/1991 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 1/1/1992

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 2/19/2025 2/19/2026
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors With Monitor 2/19/2025 2/19/2026
Overfill Prev Device Overfill Drop Tube Valve 2/19/2025 2/19/2028
Piping Fiberglass Double Wall N/A N/A
Piping Flex Connector Steel N/A N/A
Piping Single Wall STP/Tanktop Sump 12/9/2022 2/19/2025
Leak Detect - Piping Sump Sensor 2/19/2025 2/19/2026
Spill Contain Device Single Wall Spill Bucket 2/19/2025 2/19/2028
Tank Fiberglass Double Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 5

Capacity: 4000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 4/30/1993 Abandoned Material:
Current Age: 33 Abandoned Date:
Install Date: 10/1/1991 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 1/1/1992

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping European with No Test Req Suction N/A N/A
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors With Monitor 2/19/2025 2/19/2026
Overfill Prev Device Overfill Drop Tube Valve 2/19/2025 2/19/2028
Piping Fiberglass Double Wall N/A N/A
Piping Flex Connector Steel N/A N/A
Piping Single Wall STP/Tanktop Sump 12/9/2022 2/19/2025
Leak Detect - Piping Sump Sensor 2/19/2025 2/19/2026
Spill Contain Device Single Wall Spill Bucket 2/19/2025 2/19/2028
Tank Fiberglass Double Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 6

Capacity: 2500 Petroleum Use: Back-up Generator
Product: Diesel Fuel CERCLA Substance:
Status: Abandoned in place CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 4/30/1993 Abandoned Material: Inert material mixed with portland cement
Current Age: 33 Abandoned Date: 4/2/2024
Install Date: 10/1/1991 Red Tag Issue Date:
Last Used Date: 9/29/2023 Fee Due: $0.00
Product Date: 1/1/1992

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 12/9/2022 12/9/2023
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors With Monitor 12/9/2022 12/9/2023
Overfill Prev Device Overfill Drop Tube Valve 12/9/2022 12/9/2025
Piping Fiberglass Double Wall N/A N/A
Piping Flex Connector Steel N/A N/A
Piping Single Wall STP/Tanktop Sump 12/9/2022 12/9/2025
Leak Detect - Piping Non-Discriminating Sump Sensor 9/9/2021 9/9/2022
Leak Detect - Piping Sump Sensor 1/24/2023 1/24/2024
Spill Contain Device Single Wall Spill Bucket 12/9/2022 12/9/2025
Tank Fiberglass Double Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date

Dispenser Information



Name\ID 1

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Not Installed UDC Sump N/A N/A



Name\ID 2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Not Installed UDC Sump N/A N/A

MFD Motorfuel Dispensing Forms

No Forms Found