Facility |
Annual Emergency Stop Inspection not completed or inspection report not available. |
1, 2, 3 |
Annual leak detection certification not completed (Required annually). |
1, 2, 3 |
Annual tank impressed current system test not completed. |
Facility |
Missing copies of 30 day Walkthrough Inspection Report. |
Facility |
Missing copies of Annual Walkthrough Inspection Report. |
1, 2, 3 |
Monthly impressed current log not available or maintained. |
1, 2, 3 |
Overfill prevention equipment inspection(s) not completed (Required every 3 years). |
1, 2, 3 |
Shear valve inspection report not completed (Required during Annual Walkthrough Inspection). |
1, 2, 3 |
Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry. |
1, 2, 3 |
Triennial spill prevention equipment testing not completed. |
1, 2, 3 |
Water in containment without required sensors – install cathodic protection on all exposed steel piping or make containment watertight. By 10/13/28, all containments must be watertight and any CP installed in containments must be removed. - All STP and Dispenser Containment |