Notice of Violations (Current)
NOV Number:
E0020262339
(Pending)
Issue Date:
10/8/2026
Expiration Date:
12/7/2026
View NOV Form
| Tanks |
Violations |
| 3, 6, 7, 8 |
Flex connector sacrificial anode system not tested (required every 3 years) - Test anodes and replace as needed - Test expired on 06/05/2026 for equipment: Corrosion Prot - Piping - Sacrificial Anode Flex Connector Dispenser 1/2
Test expired on 06/05/2026 for equipment: Corrosion Prot - Piping - Sacrificial Anode Flex Connector Dispenser 11
Test expired on 06/05/2026 for equipment: Corrosion Prot - Piping - Sacrificial Anode Flex Connector Dispenser 3/4
Test expired on 06/05/2026 for equipment: Corrosion Prot - Piping - Sacrificial Anode Flex Connector Dispenser 5/6
Test expired on 06/05/2026 for equipment: Corrosion Prot - Piping - Sacrificial Anode Flex Connector Dispenser 7/8
Test expired on 06/05/2026 for equipment: Corrosion Prot - Piping - Sacrificial Anode Flex Connector Dispenser 9/10 |
| 3, 6, 7, 8 |
Overfill prevention equipment inspection(s) not completed (Required every 3 years). - Test expired on 06/05/2026 for equipment: Overfill Prev Device - Ball Float Vent Valve OPW 53
Test expired on 06/05/2026 for equipment: Overfill Prev Device - Overfill Drop Tube Valve |
| 3, 6, 7, 8 |
Triennial spill prevention equipment testing not completed. - Test expired on 06/05/2026 for equipment: Spill Contain Device - Single Wall Spill Bucket |