Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 5002518
Status: Active
Facility Name: Fast Stop
Address: 705 Old Route 36
Illiopolis, IL 62539
County: Sangamon
Property Parcel: 17-12.0-426-010
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: X000123
Green Tag Issue Date: 2/15/2022
Green Tag Expiration Date: 12/31/2024

Owner Details

Owner Name: BPS Oil Corporation
Owner Address: 705 Old Route 36
Illiopolis, IL 62539
Owner Status: Current Owner
Purchase Date: 3/23/2005
Type of Financial Responsibility: Designated Savings Account
Financial Responsibility Reporting Due Date: 12/19/2024

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 2/15/2022 12/31/2024

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0035087 BPS Oil Corporation Current Owner 3/23/2005
U0032781 Medici Enterprise, Inc. Former Owner 3/23/2005
U0023509 Ramsey, Jerry Former Owner 8/1/1990
U0009028 Lee Paul Former Owner 12/31/1967

Permits (Unexpired)

Click for permit history

No Active Permits Found

Deficiencies (Current)

NOV Number: E0020241471 (Pending)    Issue Date: 5/28/2024    Expiration Date: 7/27/2024    View NOV Form

Tanks Deficiency
Facility Missing copy of written UST facility operation & maintenance plan
4, 5, 6 Overfill prevention equipment inspection(s) not completed (Required every 3 years).
4, 5, 6 Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry. - Fluids in all spill buckets.
4, 5, 6 Triennial spill prevention equipment testing not completed.
4, 5, 6 Triennial testing for qualifying piping containment sump not completed (Required every 3 years).

IEMA Numbers Associated with the Facility

IEMA Number Inspection Date Inspection Type Permit Number
05-0961 3/24/2009 Abandonment Log 00240-2009ABN
16-0832 11/9/2016 Abandonment Log 01312-2016ABN
2021-0405 4/29/2021 Removal Log 00462-2021REM
2021-0405 4/27/2021 Removal Log 00462-2021REM
2021-0405 5/6/2021 Removal Log 00462-2021REM

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
05-0961 Eligible 9/12/2005 9/27/2005 $10,000
05-0961 Eligible 6/3/2015 6/18/2015 $10,000
20160832 Eligible 10/26/2016 10/27/2016 $5,000 Letter
20210405 Eligible 7/19/2021 7/22/2021 $5,000 Letter
Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 6000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 4/27/2021
OSFM First Notify Date: 3/18/1986 Abandoned Material: Inert material mixed with portland cement
Current Age: Abandoned Date: 3/24/2009
Install Date: Red Tag Issue Date:
Last Used Date: 10/12/2005 Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Tank Steel Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 2

Capacity: 8000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 4/27/2021
OSFM First Notify Date: 3/18/1986 Abandoned Material:
Current Age: Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Isolation Boots Flex Connector N/A N/A
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Lining Materials Internal 4/28/2015 4/28/2020
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 5/1/2020 5/1/2021
Leak Detect - Tank Automatic Tank Gauging Incon TS 1001 5/1/2020 5/1/2021
Overfill Prev Device Overfill Drop Tube Valve 11/6/2019 11/6/2022
Piping Flex Connector Steel N/A N/A
Piping Fiberglass Single Wall Piping N/A N/A
Piping Not Installed STP/Tanktop Sump N/A N/A
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A
Spill Contain Device Single Wall Spill Bucket 5/1/2020 5/1/2023
Tank Steel Single Wall N/A N/A
Vent, Riser, Fill Piping Steel risers N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Single Wall Piping Precision Test Pass 5/1/2020



Tank Number 3

Capacity: 8000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 4/29/2021
OSFM First Notify Date: 3/18/1986 Abandoned Material: Inert material mixed with portland cement
Current Age: Abandoned Date: 11/9/2016
Install Date: Red Tag Issue Date:
Last Used Date: 4/27/2015 Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Isolation Boots Flex Connector N/A N/A
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Lining Materials Internal 5/6/2010 5/6/2015
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 1/20/2014 1/20/2015
Leak Detect - Tank Automatic Tank Gauging Incon TS 1001
Overfill Prev Device Overfill Drop Tube Valve
Piping Flex Connector Steel N/A N/A
Piping Fiberglass Single Wall Piping N/A N/A
Spill Contain Device Single Wall Spill Bucket
Tank Steel Single Wall N/A N/A
Vent, Riser, Fill Piping Steel risers N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 4

Capacity: 14000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 1/5/2021 Abandoned Material:
Current Age: 3 Abandoned Date:
Install Date: 12/3/2020 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 7/26/2023 7/26/2024
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 450 Plus 7/26/2023 7/26/2024
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 7/26/2023 7/26/2024
Overfill Prev Device Overfill Drop Tube Valve 4/6/2021 4/6/2024
Piping Flexible Double Wall A.P.T. Poly Tech P175SC N/A N/A
Piping Single Wall STP/Tanktop Sump 1/21/2021 1/21/2024
Leak Detect - Piping Sump Sensor with positive shutdown 7/26/2023 7/26/2024
Spill Contain Device Single Wall Spill Bucket 1/21/2021 1/21/2024
Tank Fiberglass Double Wall Containment Solutions N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall A.P.T. Poly Tech P175SC Precision Test Pass 7/26/2023
Tank Fiberglass Double Wall Containment Solutions Precision Test (Tank) Pass 4/6/2021



Tank Number 5

Capacity: 10000 Petroleum Use: None
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 1/5/2021 Abandoned Material:
Current Age: 3 Abandoned Date:
Install Date: 12/3/2020 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 7/26/2023 7/26/2024
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 450 Plus 7/26/2023 7/26/2024
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 7/26/2023 7/26/2024
Overfill Prev Device Overfill Drop Tube Valve 4/6/2021 4/6/2024
Piping Flexible Double Wall A.P.T. Poly Tech P175SC N/A N/A
Piping Single Wall STP/Tanktop Sump 1/21/2021 1/21/2024
Leak Detect - Piping Sump Sensor with positive shutdown 7/26/2023 7/26/2024
Spill Contain Device Single Wall Spill Bucket 1/21/2021 1/21/2024
Tank Fiberglass Double Wall Containment Solutions N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall A.P.T. Poly Tech P175SC Precision Test Pass 7/26/2023
Tank Fiberglass Double Wall Containment Solutions Precision Test (Tank) Pass 4/6/2021



Tank Number 6

Capacity: 6000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 1/5/2021 Abandoned Material:
Current Age: 3 Abandoned Date:
Install Date: 12/3/2020 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 7/26/2023 7/26/2024
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 450 Plus 7/26/2023 7/26/2024
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 7/26/2023 7/26/2024
Overfill Prev Device Overfill Drop Tube Valve 4/6/2021 4/6/2024
Piping Flexible Double Wall A.P.T. Poly Tech P175SC N/A N/A
Piping Single Wall STP/Tanktop Sump 1/21/2021 1/21/2024
Leak Detect - Piping Sump Sensor with positive shutdown 7/26/2023 7/26/2024
Spill Contain Device Single Wall Spill Bucket 1/21/2021 1/21/2024
Tank Fiberglass Double Wall Containment Solutions N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall A.P.T. Poly Tech P175SC Precision Test Pass 7/26/2023
Tank Fiberglass Double Wall Containment Solutions Precision Test (Tank) Pass 4/6/2021



Tank Number 7

Capacity: 2000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 5/6/2021
OSFM First Notify Date: 4/29/2021 Abandoned Material:
Current Age: Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 8

Capacity: 2000 Petroleum Use: None
Product: Diesel Fuel CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 5/6/2021
OSFM First Notify Date: 4/29/2021 Abandoned Material:
Current Age: Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 1/21/2021 1/21/2024
Leak Detect - Piping Sump Sensor with positive shutdown 7/26/2023 7/26/2024



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Sump Sensor with positive shutdown 7/26/2023 7/26/2024



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Sump Sensor with positive shutdown 7/26/2023 7/26/2024



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 1/21/2021 1/21/2024
Leak Detect - Piping Sump Sensor with positive shutdown 7/26/2023 7/26/2024



Name\ID 9

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 1/21/2021 1/21/2024
Leak Detect - Piping Sump Sensor with positive shutdown 7/26/2023 7/26/2024



Name\ID 9S

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 1/21/2021 1/21/2024
Leak Detect - Piping Sump Sensor with positive shutdown 7/26/2023 7/26/2024

MFD Motorfuel Dispensing Forms

Facility Number Name City Received Date Letter
5002518 Fast Stop Illiopolis 03/30/2021 Letter Form