Owner Summary
Click for Facility/Tank Ownership history
| Owner Number |
Owner Name |
Owner Status |
Purchase Date |
| U0030051 |
Ahlstrom Filtration, LLC |
Current Owner |
1/17/2001 |
| U0005779 |
Georgia Pacific Corporation |
Former Owner |
|
Notice of Violations (Current)
NOV Number:
E0020261147
(Pending)
Issue Date:
4/29/2026
Expiration Date:
6/28/2026
View NOV Form
| Tanks |
Violations |
| 2, 3, 4, 5 |
Annual leak detection certification not completed (Required annually). - Expired 2/4/2026 and needs to be performed. |
| 2, 3, 4, 5 |
Line interstitial sensor functional test not accomplished (Required annually). - Sump sensor expired 2/4/2026 and needs to be performed. |
| 2, 3, 4, 5 |
Tank interstitial sensor functional test not accomplished (Required annually). - Expired 2/4/2026 and needs to be performed. |
IEMA Numbers Associated with the Facility
| IEMA Number |
Inspection Date |
Inspection Type |
Permit Number |
| 94-1734 |
8/3/1994 |
Removal Log |
|
LUST
Fund Eligibility and Deductibility Determinations
| IEMA Number |
Status |
OSFM Received Date |
OSFM Response Date |
Deductible |
Letter |
| 94-1734 |
Eligible |
2/22/1995
|
3/24/1995
|
$10,000
|
|
Tank Number 1
| Capacity: |
500 |
|
Petroleum Use: |
|
| Product: |
Gasoline |
|
CERCLA Substance: |
|
| Status: |
Removed |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
8/3/1994 |
|
OSFM
First Notify Date: |
3/1/1986 |
|
Abandoned Material: |
|
| Current Age: |
|
|
Abandoned Date: |
|
| Install Date: |
|
|
Red Tag Issue Date: |
|
| Last Used Date: |
3/1/1976 |
|
Fee Due: |
$0.00 |
| Product Date: |
|
|
|
|
Equipment Information
No Equipment Listed
Additional Tests
No Tests Listed
Tank Number 2
| Capacity: |
20000 |
|
Petroleum Use: |
|
| Product: |
Phenol |
|
CERCLA Substance: |
Phenol |
| Status: |
Currently in use |
|
CAS Code: |
108-95-2 |
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
3/30/2001 |
|
Abandoned Material: |
|
| Current Age: |
25 |
|
Abandoned Date: |
|
| Install Date: |
1/17/2001 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
2/26/2001 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Composite Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
European with No Test Req Suction |
Not applicable |
Not applicable |
|
Leak Detect - Tank
|
Automatic Tank Gauging Veeder Root TLS 450 with CSLD |
6/23/2026 |
6/23/2027 |
|
Leak Detect - Tank
|
Non-Discriminating Interstitial Monitoring Sensors |
6/23/2026 |
6/23/2027 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
2/6/2025 |
2/6/2028 |
|
Piping
|
Fiberglass Chase |
Not applicable |
Not applicable |
|
Piping
|
Flex Connector Steel |
Not applicable |
Not applicable |
|
Piping
|
Steel Single Wall Piping |
Not applicable |
Not applicable |
|
Piping
|
Single Wall STP/Tanktop Sump |
2/6/2025 |
2/6/2028 |
Leak Detect - Piping
|
Sump Sensor |
2/6/2025 |
2/6/2028 |
|
Spill Contain Device
|
Single Wall Spill Bucket |
2/6/2025 |
2/6/2028 |
|
Tank
|
Composite Double Wall Modern Welding Glasteel II |
Not applicable |
Not applicable |
Additional Tests
No Tests Listed
Tank Number 3
| Capacity: |
20000 |
|
Petroleum Use: |
|
| Product: |
Phenol |
|
CERCLA Substance: |
Phenol |
| Status: |
Currently in use |
|
CAS Code: |
108-95-2 |
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
3/30/2001 |
|
Abandoned Material: |
|
| Current Age: |
25 |
|
Abandoned Date: |
|
| Install Date: |
1/17/2001 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
2/26/2001 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Composite Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
European with No Test Req Suction |
Not applicable |
Not applicable |
|
Leak Detect - Tank
|
Automatic Tank Gauging Veeder Root TLS 450 with CSLD |
6/23/2026 |
6/23/2027 |
|
Leak Detect - Tank
|
Non-Discriminating Interstitial Monitoring Sensors |
6/23/2026 |
6/23/2027 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
2/6/2025 |
2/6/2028 |
|
Piping
|
Fiberglass Chase |
Not applicable |
Not applicable |
|
Piping
|
Flex Connector Steel |
Not applicable |
Not applicable |
|
Piping
|
Steel Single Wall Piping |
Not applicable |
Not applicable |
|
Piping
|
Single Wall STP/Tanktop Sump |
2/6/2025 |
2/6/2028 |
Leak Detect - Piping
|
Sump Sensor |
2/6/2025 |
2/6/2028 |
|
Spill Contain Device
|
Single Wall Spill Bucket |
2/6/2025 |
2/6/2028 |
|
Tank
|
Composite Double Wall Modern Welding Glasteel II |
Not applicable |
Not applicable |
Additional Tests
No Tests Listed
Tank Number 4
| Capacity: |
20000 |
|
Petroleum Use: |
|
| Product: |
Methanol |
|
CERCLA Substance: |
Methanol |
| Status: |
Currently in use |
|
CAS Code: |
67-56-1 |
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
3/30/2001 |
|
Abandoned Material: |
|
| Current Age: |
25 |
|
Abandoned Date: |
|
| Install Date: |
1/17/2001 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
2/26/2001 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Composite Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
European with No Test Req Suction |
Not applicable |
Not applicable |
|
Leak Detect - Tank
|
Automatic Tank Gauging Veeder Root TLS 450 with CSLD |
6/23/2026 |
6/23/2027 |
|
Leak Detect - Tank
|
Non-Discriminating Interstitial Monitoring Sensors |
6/23/2026 |
6/23/2027 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
2/6/2025 |
2/6/2028 |
|
Piping
|
Fiberglass Chase |
Not applicable |
Not applicable |
|
Piping
|
Flex Connector Steel |
Not applicable |
Not applicable |
|
Piping
|
Steel Single Wall Piping |
Not applicable |
Not applicable |
|
Piping
|
Single Wall STP/Tanktop Sump |
2/6/2025 |
2/6/2028 |
Leak Detect - Piping
|
Sump Sensor |
2/6/2025 |
2/6/2028 |
|
Spill Contain Device
|
Single Wall Spill Bucket |
2/6/2025 |
2/6/2028 |
|
Tank
|
Composite Double Wall Modern Welding Glasteel II |
Not applicable |
Not applicable |
Additional Tests
No Tests Listed
Tank Number 5
| Capacity: |
20000 |
|
Petroleum Use: |
|
| Product: |
Methanol |
|
CERCLA Substance: |
Methanol |
| Status: |
Currently in use |
|
CAS Code: |
67-56-1 |
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
3/30/2001 |
|
Abandoned Material: |
|
| Current Age: |
25 |
|
Abandoned Date: |
|
| Install Date: |
1/17/2001 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
2/26/2001 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Composite Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
European with No Test Req Suction |
Not applicable |
Not applicable |
|
Leak Detect - Tank
|
Automatic Tank Gauging Veeder Root TLS 450 with CSLD |
6/23/2026 |
6/23/2027 |
|
Leak Detect - Tank
|
Non-Discriminating Interstitial Monitoring Sensors |
6/23/2026 |
6/23/2027 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
2/6/2025 |
2/6/2028 |
|
Piping
|
Fiberglass Chase |
Not applicable |
Not applicable |
|
Piping
|
Flex Connector Steel |
Not applicable |
Not applicable |
|
Piping
|
Steel Single Wall Piping |
Not applicable |
Not applicable |
|
Piping
|
Single Wall STP/Tanktop Sump |
2/6/2025 |
2/6/2028 |
Leak Detect - Piping
|
Sump Sensor |
2/6/2025 |
2/6/2028 |
|
Spill Contain Device
|
Single Wall Spill Bucket |
2/6/2025 |
2/6/2028 |
|
Tank
|
Composite Double Wall Modern Welding Glasteel II |
Not applicable |
Not applicable |
Additional Tests
No Tests Listed
Failed test = the latest test has failed.
Not applicable = a test does not apply to this equipment type or configuration.
No passing test found = a passing test is expected but was not found from the source data.
Dispenser Information
Failed test = the latest test has failed.
Not applicable = a test does not apply to this equipment type or configuration.
No passing test found = a passing test is expected but was not found from the source data.
MFD
Motorfuel Dispensing Forms
No Forms Found