Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 4039778
Status: Active
Facility Name: Murphy Oil USA #6554
Address: 105 Dettro Drive
Mattoon, IL 61938
County: Coles
Property Parcel: 06-0-00578-001
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: AA00377
Green Tag Issue Date: 2/26/2025
Green Tag Expiration Date: 12/31/2027

Owner Details

Owner Name: Murphy Oil USA, Inc.
Owner Address: 200 E. Peach Street
El Dorado, AR 71730
Owner Status: Current Owner
Purchase Date:
Type of Financial Responsibility: Self-Insurance
Financial Responsibility Reporting Due Date: 6/29/2026

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 2/26/2025 12/31/2027

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0029289 Murphy Oil USA, Inc. Current Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violations (Current)

NOV Number: E0020251197 (Pending)    Issue Date: 5/7/2025    Expiration Date: 7/6/2025    View NOV Form

Tanks Violation
1, 2, 3 Line leak detection equipment in alarm or failed test, must repair or replace. - Sump sensors.
1, 2, 3 Miscellaneous - Requires maintenance.
1, 2, 3 Tank interstitial sensors in alarm or failed test, must repair or replace. - Interstitial sensors.

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 12000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 8/14/2000 Abandoned Material:
Current Age: 24 Abandoned Date:
Install Date: 7/14/2000 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 8/8/2000

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 5/5/2025 5/5/2026
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors With Monitor 5/14/2025 5/14/2026
Overfill Prev Device Overfill Drop Tube Valve 5/22/2024 5/22/2027
Piping Flexible Double Wall N/A N/A
Piping Single Wall STP/Tanktop Sump 9/14/2023 9/14/2026
Leak Detect - Piping Sump Sensor 5/22/2024 4/21/2025
Spill Contain Device Single Wall Spill Bucket 6/23/2023 6/23/2026
Tank Fiberglass Double Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall Precision Test (Piping) Pass 4/22/2025



Tank Number 2

Capacity: 8000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 8/14/2000 Abandoned Material:
Current Age: 24 Abandoned Date:
Install Date: 7/14/2000 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 8/8/2000

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 4/22/2025 4/22/2026
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors With Monitor 5/14/2025 5/14/2026
Overfill Prev Device Overfill Drop Tube Valve 5/22/2024 5/22/2027
Piping Flexible Double Wall N/A N/A
Piping Single Wall STP/Tanktop Sump 9/14/2023 9/14/2026
Leak Detect - Piping Sump Sensor 5/22/2024 4/22/2025
Spill Contain Device Single Wall Spill Bucket 6/23/2023 6/23/2026
Tank Fiberglass Double Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall Precision Test (Piping) Pass 4/22/2025



Tank Number 3

Capacity: 4000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 8/14/2000 Abandoned Material:
Current Age: 24 Abandoned Date:
Install Date: 7/14/2000 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 8/8/2000

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 4/22/2025 4/22/2026
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors With Monitor 5/14/2025 5/14/2026
Overfill Prev Device Overfill Drop Tube Valve 5/22/2024 5/22/2027
Piping Flexible Double Wall N/A N/A
Piping Single Wall STP/Tanktop Sump 9/14/2023 9/14/2026
Leak Detect - Piping Sump Sensor 5/22/2024 4/22/2025
Spill Contain Device Single Wall Spill Bucket 6/23/2023 6/23/2026
Tank Fiberglass Double Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall Precision Test (Piping) Pass 4/22/2025

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 9/14/2023 9/14/2026
Leak Detect - Piping Sump Sensor 5/22/2024 4/22/2025



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 9/14/2023 9/14/2026
Leak Detect - Piping Sump Sensor 5/22/2024 4/22/2025



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 9/14/2023 9/14/2026
Leak Detect - Piping Sump Sensor 5/22/2024 4/22/2025



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 9/14/2023 9/14/2026
Leak Detect - Piping Sump Sensor 5/22/2024 4/22/2025

MFD Motorfuel Dispensing Forms