Notice of Violatlions (Current)
NOV Number:
E0020261067
(Pending)
Issue Date:
4/21/2026
Expiration Date:
6/20/2026
View NOV Form
| Tanks |
Violations |
| 1, 2, 3, 4 |
Line interstitial sensor functional test not accomplished (Required annually). - Tanks 1,2and 3. UDC'S 3/4 and 5/6. |
| 4 |
Line interstitial sensors have been raised and rendered inoperational. |
| 1, 2, 3, 4 |
Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry. |
| 1, 2, 3, 4 |
Water in containment with required interstitial sensors - Remove water and repair containments to prevent water ingress. |