Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 4028704
Status: Active
Facility Name: Qik-N-EZ #60
Address: 1510 East Vernon
Normal, IL 61761
County: McLean
Property Parcel: 14-26-377-005
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Z002050
Green Tag Issue Date: 11/1/2024
Green Tag Expiration Date: 12/31/2026

Owner Details

Owner Name: Qik N EZ Properties, LLC
Owner Address: 2026 Republic
Springfield, IL 62702
Owner Status: Current Owner
Purchase Date: 1/15/1997
Type of Financial Responsibility: Self-Insurance
Financial Responsibility Reporting Due Date: 6/28/2025

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 11/1/2024 12/31/2026

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0025673 Qik N EZ Properties, LLC Current Owner 1/15/1997
U0018296 Verkler Ken Former Owner 12/31/1967

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violations (Current)

No Notice of Violations Found

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
98-1263 Eligible 7/9/1998 8/3/1998 $10,000
20210033 Eligible 8/26/2021 9/1/2021 $5,000 Letter
Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 10000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 10/5/1995 Abandoned Material:
Current Age: 33 Abandoned Date:
Install Date: 12/1/1991 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 5/1/1992

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Sacrificial Anode Flex Connector 4/17/2024 4/17/2027
Corrosion Prot - Piping Sacrificial Anode Flex Connector 4/17/2024 4/17/2027
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 4/29/2025 4/29/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 4/29/2025 4/29/2026
Overfill Prev Device Overfill Drop Tube Valve 4/17/2024 4/17/2027
Piping Flex Connector Steel N/A N/A
Piping Fiberglass Single Wall Piping N/A N/A
Piping Single Wall STP/Tanktop Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A
Spill Contain Device Single Wall Spill Bucket 4/17/2024 4/17/2027
Tank Fiberglass Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Single Wall Piping Precision Test (Piping) Pass 4/29/2025



Tank Number 2

Capacity: 10000 Petroleum Use:
Product: Gasoline - Non Ethanol CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 10/5/1995 Abandoned Material:
Current Age: 33 Abandoned Date:
Install Date: 12/1/1991 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 5/1/1992

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Sacrificial Anode Flex Connector 4/17/2024 4/17/2027
Corrosion Prot - Piping Sacrificial Anode Flex Connector 4/17/2024 4/17/2027
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 4/29/2025 4/29/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 4/29/2025 4/29/2026
Overfill Prev Device Overfill Drop Tube Valve 4/17/2024 4/17/2027
Piping Flex Connector Steel N/A N/A
Piping Fiberglass Single Wall Piping N/A N/A
Piping Single Wall STP/Tanktop Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A
Spill Contain Device Single Wall Spill Bucket 4/17/2024 4/17/2027
Tank Fiberglass Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Single Wall Piping Precision Test (Piping) Pass 4/29/2025



Tank Number 3

Capacity: 10000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 10/5/1995 Abandoned Material:
Current Age: 33 Abandoned Date:
Install Date: 12/1/1991 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 5/1/1992

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Sacrificial Anode Flex Connector 4/17/2024 4/17/2027
Corrosion Prot - Piping Sacrificial Anode Flex Connector 4/17/2024 4/17/2027
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 4/29/2025 4/29/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 4/29/2025 4/29/2026
Overfill Prev Device Overfill Drop Tube Valve 4/17/2024 4/17/2027
Piping Flex Connector Steel N/A N/A
Piping Fiberglass Single Wall Piping N/A N/A
Piping Single Wall STP/Tanktop Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A
Spill Contain Device Single Wall Spill Bucket 4/17/2024 4/17/2027
Tank Fiberglass Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Single Wall Piping Precision Test (Piping) Pass 4/29/2025



Tank Number 4

Capacity: 10000 Petroleum Use:
Product: Gasoline - Non Ethanol CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 10/5/1995 Abandoned Material:
Current Age: 33 Abandoned Date:
Install Date: 12/1/1991 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 5/1/1992

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 4/29/2025 4/29/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 4/29/2025 4/29/2026
Overfill Prev Device Overfill Drop Tube Valve 4/17/2024 4/17/2027
Piping Flex Connector Steel N/A N/A
Piping Fiberglass Single Wall Piping N/A N/A
Piping Single Wall STP/Tanktop Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A
Spill Contain Device Single Wall Spill Bucket 4/17/2024 4/17/2027
Tank Fiberglass Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Single Wall Piping Precision Test (Piping) Pass 4/29/2025



Tank Number 5

Capacity: 4000 Petroleum Use: None
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 9/30/1997 Abandoned Material:
Current Age: 27 Abandoned Date:
Install Date: 6/6/1997 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 6/7/1997

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 4/29/2025 4/29/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 4/29/2025 4/29/2026
Overfill Prev Device Overfill Drop Tube Valve 4/17/2024 4/17/2027
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Flex Connector Steel N/A N/A
Piping Single Wall STP/Tanktop Sump 4/17/2024 4/17/2027
Leak Detect - Piping Sump Sensor with positive shutdown 4/29/2025 4/29/2026
Spill Contain Device Single Wall Spill Bucket 4/17/2024 4/17/2027
Tank Fiberglass Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX Precision Test (Piping) Pass 4/29/2025

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Not Installed UDC Sump N/A N/A



Name\ID 11/12

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 13/14

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 15/16

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 4/17/2024 4/17/2027
Leak Detect - Piping Sump Sensor with positive shutdown 4/29/2025 4/29/2026



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 9/10

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Not Installed UDC Sump N/A N/A

MFD Motorfuel Dispensing Forms

No Forms Found