Notice of Violations (Current)
NOV Number:
E0020250821
(Pending)
Issue Date:
3/27/2025
Expiration Date:
5/26/2025
View NOV Form
Tanks |
Violation |
1, 2 |
Line interstitial sensors have been raised and rendered inoperational. - Dispenser 3/4 has a raised sensor and has 2" of product at bottom of UDC. Product needs removed and sensor lowered. |
Facility |
Miscellaneous - Shear valve leaking on dispenser 3/4. Fluids in the containment. Repair or replace to prevent further
release.
Section 175.720 Defective or Non-Compliant Equipment and Emergency Action by OSFM
a)Pursuant to Section 6 of the Gasoline Storage Act [430 ILCS 15/6], whenever necessary or
appropriate to assure that the public health or safety is not threatened, OSFM shall have the authority to undertake emergency action whenever there is a release or substantial threat of a release of petroleum or regulated substances from a UST. |