5, 6, 7 |
Failed to Empty the Tank to 1" or Less - Per 175.810(a)(1), when placing tanks out of service, the tank and lines must be emptied immediately. The UST is considered empty when all materials have been removed to one inch or less. Upon an inspection conducted on 7/7/23, stick readings verified that there was at least 6 inches of product in tanks 5, 6 & 7. These three tanks have been red tagged since 3/7/18. |
Facility |
Financial responsibility must be reported yearly - Per 41 Ill. Adm. Code 176.220, tank owners/operators must submit an electronic Financial Responsibility Report form on an annual basis. Financial Responsibility must be maintained until the tank is removed or properly abandoned in place by a licensed UST decommissiong contractor. The form can be found at: https://webapps.sfm.illinois.gov/USTPortal/Forms/FinancialResponsibility. |
5, 6, 7 |
Remove tank(s) - Single-Walled, Over 30 Years Old and OOS Over One Year - The single walled tanks were taken out of service on 2/5/18, and are 36 years old. Per 175.810(e) tanks must be removed as they are now condemned. Here is a link to the licensed UST Decommissioning contractors, that can perform UST tank |
Facility |
Submit Notification Form For Ownership Change - Per 41 Ill. Adm. Code 176.440 (g), a change of ownership information must be reported on an electronic Notification for Underground Storage Tank form. According to the current property deed on file with McLean County Illinois, the property was conveyed to “Bloom Fuel, Inc. on March 1, 2007. The Notification Form is available at: https://webapps.sfm.illinois.gov/USTPortal/NotificationForm. |