Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 4021725
Status: Active
Facility Name: G & G of Paris, Inc. - Citgo
Address: 813 S. Central Ave.
Paris, IL 61944
County: Edgar
Property Parcel:
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Y001576
Green Tag Issue Date: 7/18/2023
Green Tag Expiration Date: 12/31/2025

Owner Details

Owner Name: G & G of Paris, Inc.
Owner Address: 813 S. Central Ave.
Paris, IL 61944
Owner Status: Current Owner
Purchase Date: 6/5/2014
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 2/28/2026

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 7/18/2023 12/31/2025

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0037327 G & G of Paris, Inc. Current Owner 6/5/2014
U0037067 United Central Bank Former Owner 5/15/2013
U0034049 KHODA Management, Inc. Former Owner 3/16/2007
U0033564 Hartman Mini Marts, Inc. Former Owner 9/1/2004
U0026809 SJC, Inc. / See USA, LLC Former Owner 5/17/1990
U0001158 Barnhart, Wm Former Owner 12/31/1967

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violations (Current)

NOV Number: E0020250521 (Pending)    Issue Date: 2/28/2025    Expiration Date: 4/29/2025    View NOV Form

Tanks Violation
Facility Farthest dispenser is greater than 40' and site lacks a communication system or system is inoperable
Facility Fire Extinguishers - 2 4A:60BC extinguishers not provided - Only Has One.
Facility Fire Extinguishers - Past due for annual testing

NOV Number: E0020250522 (Pending)    Issue Date: 2/28/2025    Expiration Date: 4/29/2025    View NOV Form

Tanks Violation
Facility A/B operator retraining required as a result of issuance of the Notice of Violation
4 Line leak detection equipment in alarm or failed test, must repair or replace. - Disp 9 has water in UDC which has sensor in it.
Facility Missing copies of 30 day Walkthrough Inspection Report.
1, 2, 3, 4 Monthly line interstitial sensor records not available.
1, 2, 3, 4 Required monthly tank leak test records not available.
1, 2, 3 Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry.
2 Submit Notification Form for Product Change - Change product to diesel.

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
97-2435 Eligible 12/9/1998 1/25/1999 $10,000
Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 10000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 5/6/1986 Abandoned Material:
Current Age: 44 Abandoned Date:
Install Date: 5/6/1981 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Sacrificial Anode Cathodic Protection 4/10/2024 4/10/2027
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 6/6/2024 6/6/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 6/6/2024 6/6/2025
Overfill Prev Device Overfill Drop Tube Valve 6/7/2022 6/7/2025
Piping Flexible Double Wall N/A N/A
Piping Single Wall STP/Tanktop Sump 6/7/2022 6/7/2025
Leak Detect - Piping Sump Sensor 6/6/2024 6/6/2025
Piping Single Wall Transition Sump 6/7/2022 6/7/2025
Leak Detect - Piping Sump Sensor 6/6/2024 6/6/2025
Piping Single Wall Transition Sump 6/7/2022 6/7/2025
Leak Detect - Piping Sump Sensor
Spill Contain Device Single Wall Spill Bucket 6/7/2022 6/7/2025
Tank STIP3 Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall Precision Test (Piping) Pass 6/6/2024



Tank Number 2

Capacity: 10000 Petroleum Use:
Product: Gasoline - Mid-grade CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 5/6/1986 Abandoned Material:
Current Age: 44 Abandoned Date:
Install Date: 5/6/1981 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Sacrificial Anode Cathodic Protection 4/10/2024 4/10/2027
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 6/6/2024 6/6/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 6/6/2024 6/6/2025
Overfill Prev Device Overfill Drop Tube Valve 6/7/2022 6/7/2025
Piping Flexible Double Wall N/A N/A
Piping Single Wall STP/Tanktop Sump 6/7/2022 6/7/2025
Leak Detect - Piping Sump Sensor 6/6/2024 6/6/2025
Piping Single Wall Transition Sump 6/7/2022 6/7/2025
Leak Detect - Piping Sump Sensor 6/6/2024 6/6/2025
Piping Single Wall Transition Sump 6/7/2022 6/7/2025
Leak Detect - Piping Sump Sensor
Spill Contain Device Single Wall Spill Bucket 6/7/2022 6/7/2025
Tank STIP3 Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall Precision Test (Piping) Pass 6/6/2024



Tank Number 3

Capacity: 10000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 5/6/1986 Abandoned Material:
Current Age: 44 Abandoned Date:
Install Date: 5/6/1981 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Sacrificial Anode Cathodic Protection 4/10/2024 4/10/2027
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 6/6/2024 6/6/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 6/6/2024 6/6/2025
Overfill Prev Device Overfill Drop Tube Valve 6/7/2022 6/7/2025
Piping Flexible Double Wall N/A N/A
Piping Single Wall STP/Tanktop Sump 6/7/2022 6/7/2025
Leak Detect - Piping Sump Sensor 6/6/2024 6/6/2025
Piping Single Wall Transition Sump 6/7/2022 6/7/2025
Leak Detect - Piping Sump Sensor 6/6/2024 6/6/2025
Piping Single Wall Transition Sump 6/7/2022 6/7/2025
Leak Detect - Piping Sump Sensor
Spill Contain Device Single Wall Spill Bucket 6/7/2022 6/7/2025
Tank STIP3 Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall Precision Test (Piping) Pass 6/6/2024



Tank Number 4

Capacity: 10000 Petroleum Use:
Product: Kerosene CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 5/6/1986 Abandoned Material:
Current Age: 44 Abandoned Date:
Install Date: 5/6/1981 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Sacrificial Anode Cathodic Protection 4/10/2024 4/10/2027
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Sacrificial Anode Cathodic Protection 4/10/2024 4/10/2027
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 6/6/2024 6/6/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 6/6/2024 6/6/2025
Overfill Prev Device Overfill Drop Tube Valve 6/7/2022 6/7/2025
Piping Flexible Double Wall N/A N/A
Piping Single Wall STP/Tanktop Sump 6/7/2022 6/7/2025
Leak Detect - Piping Sump Sensor 6/6/2024 6/6/2025
Spill Contain Device Single Wall Spill Bucket 6/7/2022 6/7/2025
Tank STIP3 Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall Precision Test (Piping) Pass 6/6/2024

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 6/7/2022 6/7/2025
Leak Detect - Piping Sump Sensor 6/6/2024 6/6/2025



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 6/7/2022 6/7/2025
Leak Detect - Piping Sump Sensor 6/6/2024 6/6/2025



Name\ID 5/6

Status: InActive
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 6/7/2022 6/7/2025
Leak Detect - Piping Sump Sensor 6/6/2024 6/6/2025



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 6/7/2022 6/7/2025
Leak Detect - Piping Sump Sensor 6/6/2024 6/6/2025



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 6/7/2022 6/7/2025
Leak Detect - Piping Sump Sensor 6/6/2024 6/6/2025



Name\ID 9

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 6/7/2022 6/7/2025
Leak Detect - Piping Sump Sensor 6/6/2024 6/6/2025

MFD Motorfuel Dispensing Forms