Notice of Violations (Current)
NOV Number:
E0020250521
(Pending)
Issue Date:
2/28/2025
Expiration Date:
4/29/2025
View NOV Form
Tanks |
Violation |
Facility |
Farthest dispenser is greater than 40' and site lacks a communication system or system is inoperable |
Facility |
Fire Extinguishers - 2 4A:60BC extinguishers not provided - Only Has One. |
Facility |
Fire Extinguishers - Past due for annual testing |
NOV Number:
E0020250522
(Pending)
Issue Date:
2/28/2025
Expiration Date:
4/29/2025
View NOV Form
Tanks |
Violation |
Facility |
A/B operator retraining required as a result of issuance of the Notice of Violation |
4 |
Line leak detection equipment in alarm or failed test, must repair or replace. - Disp 9 has water in UDC which has sensor in it. |
Facility |
Missing copies of 30 day Walkthrough Inspection Report. |
1, 2, 3, 4 |
Monthly line interstitial sensor records not available. |
1, 2, 3, 4 |
Required monthly tank leak test records not available. |
1, 2, 3 |
Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry. |
2 |
Submit Notification Form for Product Change - Change product to diesel. |