Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 4015557
Status: Active
Facility Name: Pontiac Citgo
Address: 212 S. Mill Street Pontiac, IL 61764
County: Livingston
Property Parcel: 15-15-22-452-003-0000
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Y003323
Green Tag Issue Date: 9/13/2023
Green Tag Expiration Date: 12/31/2025

Owner Details

Owner Name: Pontiac 66, LLC
Owner Address: 212 S. Mill Street Pontiac, IL 61764
Owner Status: Current Owner
Purchase Date: 2/8/2023
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 4/2/2026

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 3/30/2023 12/31/2025

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0040861 Pontiac 66, LLC Current Owner 2/8/2023
U0038679 DM Patel, LLC Former Owner 2/10/2017
U0034501 Naqvi, Hameed Former Owner 10/17/2007
U0033157 Mulligan Petro, Inc. Former Owner 6/27/2005
U0029349 Wyllie, John Former Owner 6/27/2005
U0033011 Singh, Dalbir Former Owner
U0010780 Myers, James Former Owner

Permits (Unexpired)

Click for permit history
Permit Number Type Status OSFM Receive Date Issue Date Expiration Date Documents
00354-2025UPG Upgrade Approved / Amended 3/25/2025 3/26/2025 9/26/2025 Documents
00771-2025UPG Upgrade Approved / Issued 6/23/2025 6/23/2025 12/23/2025 Documents

Notice of Violatlions (Current)

NOV Number: E0020250782 (Referred to Legal)    Issue Date: 3/25/2025    Expiration Date: 5/24/2025    View NOV Form

Tanks Violations
Facility Facility Operation and Maintenance Plan not completed or available.
5, 6 Line leak detection equipment in alarm or failed test, must repair or replace. - ELLDs failed test. Tanks 5 and 6 red tagged due to no line leak detection. Note: Contractor was onsite to replace these when STSS was onsite. STSS informed by technician that Tank 5 ELLD could not be accessed. Tank 6 was replaced but no permit was filed at the time of inspection.
5 Miscellaneous - Sump sensor failed test. Repair or replace.
Facility Missing copies of current testing certificates for operator training - Testing certificate for the AB is not available.
Facility Missing list of designated Class A/B & C Operators
5, 6, 7 Monthly line interstitial sensor records not available.
5, 6, 7 Required monthly tank leak test records not available.
7 Tank monitor does not appear to function properly and requires maintenance. - ATG is in alarm for tank 7. Repair or replace. Dates are not correct on ATG. Correct the date. Date is reported as 01/24/2036.

NOV Number: E0020251440 (Pending)    Issue Date: 6/4/2025    Expiration Date: 6/4/2025    View NOV Form

Tanks Violations
Facility No certified employees on site at an attended dispensing facilitiy.

IEMA Numbers Associated with the Facility

IEMA Number Inspection Date Inspection Type Permit Number
99-2459 12/8/1999 Removal Log 03514-1999REM

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
99-2459 Eligible 12/15/1999 12/22/1999 $15,000
Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 4000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 12/8/1999
OSFM First Notify Date: 4/14/1986 Abandoned Material:
Current Age: 45 Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: 12/15/1998 Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 2

Capacity: 6000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 12/8/1999
OSFM First Notify Date: 4/14/1986 Abandoned Material:
Current Age: 45 Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: 12/15/1998 Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 3

Capacity: 500 Petroleum Use:
Product: Used Oil CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 12/8/1999
OSFM First Notify Date: 4/14/1986 Abandoned Material:
Current Age: 45 Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 4

Capacity: 1000 Petroleum Use:
Product: Heating Oil CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 12/8/1999
OSFM First Notify Date: 11/22/1999 Abandoned Material:
Current Age: Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: 12/15/1998 Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 5

Capacity: 8000 Petroleum Use: None
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 1/19/2001 Abandoned Material:
Current Age: 24 Abandoned Date:
Install Date: 8/17/2000 Red Tag Issue Date: 6/4/2025
Last Used Date: Fee Due: $0.00
Product Date: 8/17/2000

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 4/1/2025 4/1/2026
Leak Detect - Tank Automatic Tank Gauging Incon TS 1001 with SCALD 1/24/2025 1/24/2026
Overfill Prev Device Ball Float Vent Valve 10/27/2022 10/27/2025
Piping Flexible Double Wall A.P.T. Poly Tech N/A N/A
Piping Single Wall STP/Tanktop Sump 10/31/2022 10/31/2025
Leak Detect - Piping Sump Sensor 10/5/2023 10/5/2024
Spill Contain Device Single Wall Spill Bucket 10/31/2022 10/31/2025
Tank Fiberglass Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall A.P.T. Poly Tech Precision Test (Piping) Pass 1/24/2025



Tank Number 6

Capacity: 10000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 1/19/2001 Abandoned Material:
Current Age: 24 Abandoned Date:
Install Date: 8/17/2000 Red Tag Issue Date: 6/4/2025
Last Used Date: Fee Due: $0.00
Product Date: 8/17/2000

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 3/25/2025 3/25/2026
Leak Detect - Tank Automatic Tank Gauging Incon TS 1001 with SCALD 1/24/2025 1/24/2026
Overfill Prev Device Ball Float Vent Valve 10/27/2022 10/27/2025
Piping Flexible Double Wall A.P.T. Poly Tech N/A N/A
Piping Single Wall STP/Tanktop Sump 10/31/2022 10/31/2025
Leak Detect - Piping Sump Sensor 1/24/2025 1/24/2026
Spill Contain Device Single Wall Spill Bucket 10/31/2022 10/31/2025
Tank Fiberglass Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall A.P.T. Poly Tech Precision Test (Piping) Pass 1/24/2025



Tank Number 7

Capacity: 12000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 1/19/2001 Abandoned Material:
Current Age: 24 Abandoned Date:
Install Date: 8/17/2000 Red Tag Issue Date: 6/4/2025
Last Used Date: Fee Due: $0.00
Product Date: 8/17/2000

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 1/24/2025 1/24/2026
Leak Detect - Tank Automatic Tank Gauging Incon TS 1001 with SCALD 1/24/2025 1/24/2026
Overfill Prev Device Ball Float Vent Valve 10/27/2022 10/27/2025
Piping Flexible Double Wall A.P.T. Poly Tech N/A N/A
Piping Single Wall STP/Tanktop Sump 10/31/2022 10/31/2025
Leak Detect - Piping Sump Sensor 1/24/2025 1/24/2026
Spill Contain Device Single Wall Spill Bucket Insert 10/31/2022 10/31/2025
Tank Fiberglass Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall A.P.T. Poly Tech Precision Test (Piping) Pass 1/24/2025

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A

MFD Motorfuel Dispensing Forms