Notice of Violations (Current)
NOV Number:
E0020232773
(Pending)
Issue Date:
12/5/2023
Expiration Date:
2/3/2024
View NOV Form
Tanks |
Violation |
3 |
Drop tube valve or overfill alarm failed inspection. Repair or replace equipment. - Repair or replace and retest and pass. Seneca failed on 10/17/23 notified OSFM 0n 12/6/23. |
NOV Number:
E0020242413
(Referred to Legal)
Issue Date:
8/28/2024
Expiration Date:
10/27/2024
View NOV Form
Tanks |
Violation |
Facility |
Miscellaneous - All water and debri must be removed from UDC'S. |
Facility |
Miscellaneous - Products lines on island that pump was removed as to be protected. |
1, 2, 3, 4, 6, 7 |
Piping interstitial must be open in all sumps - Boots on all STP'S and UDC'S on product lines must be loosened. |
1, 2, 3, 4, 6 |
Tank monitor does not appear to function properly and requires maintenance. - Alarms going off. |
1, 2, 3, 4, 6, 7 |
Triennial testing for qualifying piping containment sump not completed (Required every 3 years). - All UDC'S are past due. |