2 |
Containment support components are cracked, deteriorated or missing. The cover and supporting components that are defective shall be replaced with factory manufactured components. - Missing handle on STP ground cover- must be removable allow for inspection. |
Facility |
Electrical Does Not Comply |
Facility |
Miscellaneous - All emergency stops are to be indicated by a sign that reads “EMERGENCY STOP” in at least 2-inch red capital letters. Control Station missing sign for Emergency Stop. |
2 |
Miscellaneous - Sensor does not appear to be functioning properly as sensor is submerged in liguid and monitor is not in alarm. |
2 |
Open electrical conduit or junction boxes. - ATG Riser - wires reconnected outside of electrical box. |
1 |
Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry. |
2 |
Water in containment with required interstitial sensors - Remove water and repair containments to prevent water ingress. |