Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 3037385
Status: Active
Facility Name: Road Ranger #186
Address: 1311 N. Carolyn Drive
Minonk, IL 61760
County: Woodford
Property Parcel:
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Y002277
Green Tag Issue Date: 1/3/2024
Green Tag Expiration Date: 12/31/2025

Owner Details

Owner Name: Road Ranger, LLC
Owner Address: 1501 Woodfield Rd., Suite 300 S
Schaumburg, IL 60173
Owner Status: Current Owner
Purchase Date: 6/15/2012
Type of Financial Responsibility: Self-Insurance
Financial Responsibility Reporting Due Date: 6/28/2025

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 1/4/2024 12/31/2025

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0033990 Road Ranger, LLC Current Owner 6/15/2012
U0010459 MKM Oil, Inc. Former Owner
U0027641 Fast Break Food Mart Inc Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violations (Current)

NOV Number: E0020250948 (Pending)    Issue Date: 4/9/2025    Expiration Date: 6/8/2025    View NOV Form

Tanks Violation
5 Annual line precision and mechanical line leak detector functional test not completed. - American with Annual precision line testing suction expired 10/18/18. (B-99)
2 Drop tube valve or overfill alarm failed inspection. Repair or replace equipment. - Failed test 3/31/2025
1, 2, 5 Line leak detection equipment in alarm or failed test, must repair or replace. - Tanks #1 (Diesel #2 (Regular) and Tank #5 (B-99) sump sensors failed testing on 3/31/25 and need repaired or replaced.
Facility Miscellaneous - Tank #2 has a cracked manhole lid covering STP and needs replaced.
1, 2, 5 Water in containment with required interstitial sensors - Remove water and repair containments to prevent water ingress. - Water in all three sumps need removed and kept dry.

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 15000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 8/13/1999 Abandoned Material:
Current Age: 25 Abandoned Date:
Install Date: 6/28/1999 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 3/31/2025 3/31/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 Plus with CSLD 3/31/2025 3/31/2026
Overfill Prev Device Overfill Drop Tube Valve 3/31/2025 3/31/2028
Piping Flexible Double Wall Total Containment Omniflex I N/A N/A
Piping Single Wall STP/Tanktop Sump 8/7/2023 8/7/2026
Leak Detect - Piping Sump Sensor 12/11/2024 3/31/2025
Piping Single Wall Transition Sump 8/7/2023 8/7/2026
Leak Detect - Piping Sump Sensor 12/11/2024 12/11/2025
Spill Contain Device Single Wall Spill Bucket 8/7/2023 8/7/2026
Tank Fiberglass Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall Total Containment Omniflex I Precision Test (Piping) Pass 12/11/2024
Tank Fiberglass Single Wall Precision Test (Tank) Pass 12/11/2024



Tank Number 2

Capacity: 15000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 8/13/1999 Abandoned Material:
Current Age: 25 Abandoned Date:
Install Date: 6/28/1999 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 3/31/2025 3/31/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 Plus with CSLD 3/31/2025 3/31/2026
Overfill Prev Device Overfill Drop Tube Valve 10/26/2022 3/31/2025
Piping Flexible Double Wall Total Containment Omniflex I N/A N/A
Piping Single Wall STP/Tanktop Sump 8/7/2023 8/7/2026
Leak Detect - Piping Sump Sensor 12/11/2024 3/31/2025
Spill Contain Device Single Wall Spill Bucket 8/7/2023 8/7/2026
Tank Fiberglass Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall Total Containment Omniflex I Precision Test (Piping) Pass 12/11/2024



Tank Number 3

Capacity: 8000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 8/13/1999 Abandoned Material:
Current Age: 25 Abandoned Date:
Install Date: 6/28/1999 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 3/31/2025 3/31/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 Plus with CSLD 3/31/2025 3/31/2026
Overfill Prev Device Overfill Drop Tube Valve 3/31/2025 3/31/2028
Piping Flexible Double Wall Total Containment Omniflex I N/A N/A
Piping Single Wall STP/Tanktop Sump 8/7/2023 8/7/2026
Leak Detect - Piping Sump Sensor 3/31/2025 3/31/2026
Spill Contain Device Single Wall Spill Bucket 8/7/2023 8/7/2026
Tank Fiberglass Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall Total Containment Omniflex I Precision Test (Piping) Pass 12/11/2024



Tank Number 4

Capacity: 8000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 8/13/1999 Abandoned Material:
Current Age: 25 Abandoned Date:
Install Date: 6/28/1999 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 3/31/2025 3/31/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 Plus with CSLD 3/31/2025 3/31/2026
Overfill Prev Device Overfill Drop Tube Valve 3/31/2025 3/31/2028
Piping Flexible Double Wall Total Containment Omniflex I N/A N/A
Piping Single Wall STP/Tanktop Sump 8/7/2023 8/7/2026
Leak Detect - Piping Sump Sensor 3/31/2025 3/31/2026
Piping Single Wall Transition Sump 8/7/2023 8/7/2026
Leak Detect - Piping Sump Sensor 12/11/2024 12/11/2025
Spill Contain Device Single Wall Spill Bucket 8/7/2023 8/7/2026
Tank Fiberglass Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall Total Containment Omniflex I Precision Test (Piping) Pass 12/11/2024
Tank Fiberglass Single Wall Precision Test (Tank) Pass 12/11/2024



Tank Number 5

Capacity: 20000 Petroleum Use:
Product: B-99 CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 10/9/2012 Abandoned Material:
Current Age: 12 Abandoned Date:
Install Date: 7/6/2012 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 7/6/2012

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping American with Annual Prec Line Testing Suction 10/18/2017 10/18/2018
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 3/31/2025 3/31/2026
Overfill Prev Device Overfill Alarm 3/31/2025 3/31/2028
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Flex Connector Steel N/A N/A
Piping Single Wall STP/Tanktop Sump 8/7/2023 8/7/2026
Leak Detect - Piping Sump Sensor with positive shutdown 12/11/2024 3/31/2025
Leak Detect - Piping Sump Sensor with positive shutdown 5/9/2025 5/9/2026
Piping Single Wall STP/Tanktop Sump 8/7/2023 8/7/2026
Leak Detect - Piping Sump Sensor with positive shutdown 3/31/2025 3/31/2026
Piping Single Wall Transition Sump 8/7/2023 8/7/2026
Leak Detect - Piping Sump Sensor with positive shutdown 12/11/2024 12/11/2025
Spill Contain Device Double Wall Spill Bucket 8/7/2023 8/7/2026
Tank Fiberglass Double Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Leak Detect - Piping American with Annual Prec Line Testing Suction Functional Pass 12/14/2023
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX Precision Test (Piping) Pass 12/14/2023
Tank Fiberglass Double Wall XERXES Precision Test (Tank) Pass 12/11/2024
Leak Detect - Tank SIR and Prec Tightness Testing Warren Rogers Assoc. Petro Network S3 Version D Precision Test (Tank) Pass 10/18/2017



Tank Number 6

Capacity: 8000 Petroleum Use:
Product: Diesel Exhaust Fluid (Non-Regulated) CERCLA Substance:
Status: Unknown CAS Code:
Regulated Status: Non-Regulated Removed Date:
OSFM First Notify Date: Abandoned Material:
Current Age: Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: Fee Due:
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 11/12

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 17

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 18/17S

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 19/18S

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 20/19S

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 21 Slave

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 21/20S

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 9/10

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID Bio Blending

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 12/14/2021 12/14/2024
Leak Detect - Piping Sump Sensor with positive shutdown 12/11/2024 12/11/2025

MFD Motorfuel Dispensing Forms

No Forms Found