Division of Petroleum & Chemical Safety

 
Pay Tank Fees Online Print Detail Page Export to Excel

Facility Details

Facility Number: 3035914
Status: Active
Facility Name: Big 10 Mart #21
Address: 1301 13th Street
East Moline, IL 61244
County: Rock Island
Property Parcel:
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Y001388
Green Tag Issue Date: 11/3/2023
Green Tag Expiration Date: 12/31/2025

Owner Details

Owner Name: Molo Oil Company
Owner Address: 123 Southern Ave.
Dubuque, IA 52003
Owner Status: Current Owner
Purchase Date: 10/3/1997
Type of Financial Responsibility: Self-Insurance
Financial Responsibility Reporting Due Date: 6/28/2025

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 11/3/2023 12/31/2025

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0010513 Molo Oil Company Current Owner 10/3/1997

Permits (Unexpired)

Click for permit history
Permit Number Type Status OSFM Receive Date Issue Date Expiration Date Documents
00561-2025CAT Cathodic Protection Approved / Issued 5/8/2025 5/8/2025 11/10/2025 Documents

Notice of Violations (Current)

NOV Number: E0020250647 (Pending)    Issue Date: 3/12/2025    Expiration Date: 5/11/2025    View NOV Form

Tanks Violation
1 Containment support components are cracked, deteriorated or missing. The cover and supporting components that are defective shall be replaced with factory manufactured components. - Square ground covers damaged and missing containment support components.
1 Containment support components are cracked, deteriorated or missing. The cover and supporting components that are defective shall be replaced with factory manufactured components. - STP ground covers containment support components deteriorated/ missing. Repair to allow for inspection.
2, 3 Containment support components are cracked, deteriorated or missing. The cover and supporting components that are defective shall be replaced with factory manufactured components. - Square ground covers damaged and missing containment support components.
3 Containment support components are cracked, deteriorated or missing. The cover and supporting components that are defective shall be replaced with factory manufactured components. - STP ground covers containment support components deteriorated/ missing. Repair to allow for inspection.
1, 2, 3 Install corrosion protection under dispensers to protect exposed flex connectors and other metal portions of product piping. - Dispensers 1/2, 3/4, 5/6, 7/8,
1, 2, 3 Water in containment without required interstitial sensors - install cathodic protection on all exposed steel. - Dispensers 1/2, 3/4, 5/6, 7/8

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information

Tank Number Capacity Product Status Regulated Status Red Tag Issued Fee Due Abandon/Removal Date
1 12000 Gasoline - Regular Currently in use Federal $0.00
2 8200 Gasoline - Premium Currently in use Federal $0.00
3 8200 Diesel Fuel Currently in use Federal $0.00

Dispenser Information

Name\ID Status
1/2 Active
3/4 Active
5/6 Active
7/8 Active

MFD Motorfuel Dispensing Forms

No Forms Found