Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 3034735
Status: Inactive
Facility Name: West K Mart
Address: 341 W. Main Street
Galesburg, IL 61401
County: Knox
Property Parcel: 99-10-380-008
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Extend
Green Tag Issue Date: 12/19/2019
Green Tag Expiration Date: 1/15/2020

Owner Details

Owner Name: Khawaja Kashif Ismail
Owner Address: 362 Clark
Galesburg, IL 61401
Owner Status: Current Owner
Purchase Date: 12/15/2016
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 4/12/2022

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 12/8/2017 12/31/2019

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0038835 Khawaja Kashif Ismail Current Owner 12/15/2016
U0013951 Sierra Petroleum Company, Inc. Former Owner 5/31/2003
U0036327 The Athans Company Former Owner 10/12/2001
U0006748 Herr Petroleum Corp. Former Owner 5/13/1996
U0034558 JSI Petroleum Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violations (Current)

NOV Number: E0020250655 (Pending)    Issue Date: 2/26/2025    Expiration Date: 4/27/2025    View NOV Form

Tanks Violation
1, 2, 3 Failed to Empty the Tank to 1" or Less - Per 175.810(a)(1), when placing tanks out of service, the tank and lines must be emptied immediately. The UST is considered empty when all materials have been removed to one inch or less. Upon my last inspection dated 1/30/25, I took a stick reading of each tank and all three tanks had more than an inch of product. Tanks have been red tagged since 1/15/20.
Facility Financial responsibility must be reported yearly - Per 176.220, tank owners/operators must submit an electronic Financial Responsibility Report form on an annual basis. Financial Responsibility must be maintained until the tanks are removed or properly abandoned in place by a licensed UST decommissiong contractor. The form can be found at: https://webapps.sfm.illinois.gov/USTPortal/Forms/FinancialResponsibility.
1, 2, 3 Remove tank(s) - Out of Service greater than 5 Years - Single walled tanks were taken out of service on 1/15/20 and are 28 years old. Per 175.810(f), if a UST is not placed back into service within 5 years from the date of last use, the tank system shall be removed within 60 days after the conclusion the 5-year period. Here is a link to the licensed UST Decommissioning contractors, that can perform UST tank removals: https://webapps.sfm.illinois.gov/ustsearch/ContractorSearch.aspx
1, 2, 3 Submit Notification Form For Tank Status Change - Per 175.810(a)(3), tanks taken out of service are required to notify the OSFM within 30 days of date of last use, on an electronic Notification for Underground Storage Tank form, declaring a tank status change. These tanks were last used on 1/15/20. Here is the link to the electronic Notification for Underground Storage Tank form, so that you can file that change: https://webapps.sfm.illinois.gov/USTPortal/NotificationForm
1, 2, 3 Tanks are condemned and must be properly decommissioned within 60 days. - Tanks were condemned as of 1/15/25.

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
03-0670 Eligible 2/10/2004 2/23/2004 $10,000
Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 12000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Condemned Tank CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 5/29/1996 Abandoned Material:
Current Age: 29 Abandoned Date:
Install Date: 5/10/1996 Red Tag Issue Date: 1/15/2020
Last Used Date: 1/15/2020 Fee Due: $0.00
Product Date: 5/10/1996

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 7/20/2018 7/20/2019
Leak Detect - Tank Automatic Tank Gauging EBW Auto-Stik Jr.
Overfill Prev Device Ball Float Vent Valve 1/7/2021 1/7/2024
Piping Flexible Double Wall N/A N/A
Piping Single Wall STP/Tanktop Sump 1/7/2021 1/7/2024
Leak Detect - Piping Sump Sensor 7/20/2018 7/20/2019
Spill Contain Device Single Wall Spill Bucket 1/7/2021 1/7/2024
Tank Fiberglass Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Tank Fiberglass Single Wall Precision Test (Tank) Pass 1/12/2021



Tank Number 2

Capacity: 12000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Condemned Tank CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 5/29/1996 Abandoned Material:
Current Age: 29 Abandoned Date:
Install Date: 5/10/1996 Red Tag Issue Date: 1/15/2020
Last Used Date: 1/15/2020 Fee Due: $0.00
Product Date: 5/10/1996

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 7/20/2018 7/20/2019
Leak Detect - Tank Automatic Tank Gauging EBW Auto-Stik Jr.
Overfill Prev Device Ball Float Vent Valve 1/7/2021 1/7/2024
Piping Flexible Double Wall A.P.T. Poly Tech P175SC N/A N/A
Piping Single Wall STP/Tanktop Sump 1/7/2021 1/7/2024
Leak Detect - Piping Sump Sensor 7/20/2018 7/20/2019
Spill Contain Device Single Wall Spill Bucket 1/7/2021 1/7/2024
Tank Fiberglass Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Tank Fiberglass Single Wall Precision Test (Tank) Pass 1/12/2021



Tank Number 3

Capacity: 8000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Condemned Tank CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 5/29/1996 Abandoned Material:
Current Age: 29 Abandoned Date:
Install Date: 5/10/1996 Red Tag Issue Date: 1/15/2020
Last Used Date: 1/15/2020 Fee Due: $0.00
Product Date: 5/10/1996

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 7/20/2018 7/20/2019
Leak Detect - Tank Automatic Tank Gauging EBW Auto-Stik Jr.
Overfill Prev Device Ball Float Vent Valve 1/7/2021 1/7/2024
Piping Flexible Double Wall A.P.T. Poly Tech P175SC N/A N/A
Piping Single Wall STP/Tanktop Sump 1/7/2021 1/7/2024
Leak Detect - Piping Sump Sensor 7/20/2018 7/20/2019
Spill Contain Device Single Wall Spill Bucket 1/7/2021 1/7/2024
Tank Fiberglass Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Tank Fiberglass Single Wall Precision Test (Tank) Pass 1/12/2021



Tank Number 4

Capacity: 560 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Pre 1974 CAS Code:
Regulated Status: Exempt Removed Date:
OSFM First Notify Date: Abandoned Material:
Current Age: Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: 12/31/1973 Fee Due:
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 1/7/2021 1/7/2024
Leak Detect - Piping Sump Sensor 7/20/2018 7/20/2019



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 1/7/2021 1/7/2024
Leak Detect - Piping Sump Sensor 7/20/2018 7/20/2019



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 1/7/2021 1/7/2024
Leak Detect - Piping Sump Sensor 7/20/2018 7/20/2019

MFD Motorfuel Dispensing Forms