Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 3025762
Status: Inactive
Facility Name: Quad City Downs, Inc.
Address: 5005 Morton Drive East Moline, IL 61244
County: Rock Island
Property Parcel: 09-28-200-005
Facility Type: Private Institution
Owner Type: Private
Green Tag Decal: P005995
Green Tag Issue Date: 11/12/2014
Green Tag Expiration Date: 12/31/2016

Owner Details

Owner Name: Quad City Downs, Inc.
Owner Address: 5005 Morton Drive East Moline, IL 61244
Owner Status: Current Owner
Purchase Date: 4/12/1988
Type of Financial Responsibility: Self-Insurance
Financial Responsibility Reporting Due Date: 9/30/2017

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Fleet 9/10/2014 12/31/2016

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0012256 Quad City Downs, Inc. Current Owner 4/12/1988

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violatlions (Current)

NOV Number: E0020212604 (Referred to Legal)    Issue Date: 9/23/2021    Expiration Date: 11/22/2021    View NOV Form

Tanks Violations
3 Remove single-wall tank(s) - Out of Service greater than 5 Years

NOV Number: E0020251816 (Pending)    Issue Date: 7/17/2025    Expiration Date: 9/15/2025    View NOV Form

Tanks Violations
3 Failed to Empty the Tank to 1" or Less - Per 175.810(a)(1), when placing tanks out of service, the tank and lines must be emptied immediately. The UST is considered empty when all materials have been removed to one inch or less.
Facility Financial responsibility must be reported yearly - Per 41 Ill. Adm. Code 176.220, tank owners/operators must submit an electronic Financial Responsibility Report form on an annual basis. Financial Responsibility must be maintained until the tank is removed or properly abandoned in place by a licensed UST decommissiong contractor. The form can be found at: https://webapps.sfm.illinois.gov/USTPortal/Forms/FinancialResponsibility.
3 Remove tank(s) - Single-Walled, Over 30 Years Old and OOS Over One Year - The remaining single walled tank was taken out of service on 5/31/16, and is 34 years old. Per 175.810(e) tanks must be removed as they are now condemned. Here is a link to the licensed UST Decommissioning contractors, that can perform UST tank removals: https://webapps.sfm.illinois.gov/ustsearch/ContractorSearch.aspx
Facility Submit Notification Form For Ownership Change - Per 41 Ill. Adm. Code 176.440 (g), a change of ownership information must be reported on an electronic Notification for Underground Storage Tank form, within 30 days of the change. According to the Rock Island County Property Tax Inquiry Portal, it states that Arlington Park Racecourse is the owner. The Notification Form is available at: https://webapps.sfm.illinois.gov/USTPortal/NotificationForm.

IEMA Numbers Associated with the Facility

IEMA Number Inspection Date Inspection Type Permit Number
90-2219 8/6/1990 Removal Log
95-0465 3/7/1995 Removal Log

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
95-0465 Eligible 4/4/1995 4/19/1995 $10,000
Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 1000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 10/5/1990
OSFM First Notify Date: 2/15/1989 Abandoned Material:
Current Age: 19 Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: 10/5/1990 Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 2

Capacity: 1000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 3/7/1995
OSFM First Notify Date: 2/15/1989 Abandoned Material:
Current Age: 16 Abandoned Date:
Install Date: 1/1/1979 Red Tag Issue Date:
Last Used Date: 3/7/1995 Fee Due: $0.00
Product Date: 1/1/1979

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 3

Capacity: 1000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Condemned Tank CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 12/14/1991 Abandoned Material:
Current Age: 35 Abandoned Date:
Install Date: 8/1/1990 Red Tag Issue Date: 5/31/2016
Last Used Date: 5/31/2016 Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Piping Other Aboveground Piping N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping European with No Test Req Suction N/A N/A
Leak Detect - Tank Vapor Monitoring
Overfill Prev Device Overfill Drop Tube Valve
Piping Aboveground N/A N/A
Piping Steel Double Wall N/A N/A
Piping Fiberglass Single Wall Piping N/A N/A
Spill Contain Device Single Wall Spill Bucket
Tank Fiberglass Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Leak Detect - Tank Vapor Monitoring Sensor Functional Pass 4/9/2014

Dispenser Information



MFD Motorfuel Dispensing Forms

No Forms Found