Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 3024552
Status: Active
Facility Name: Moline Gas Food and Liquor
Address: 3328 Avenue of the Cities
Moline, IL 61265
County: Rock Island
Property Parcel: 17-04-406-271
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: X003104
Green Tag Issue Date: 3/2/2023
Green Tag Expiration Date: 12/31/2024

Owner Details

Owner Name: Koujha Corp.
Owner Address: 406 Main Street
P.O. Box 205
New Windsor, IL 61465
Owner Status: Current Owner
Purchase Date: 4/30/2012
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 3/2/2024

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 11/22/2022 12/31/2024

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0036535 Koujha Corp. Current Owner 4/30/2012
U0034908 Saru Food Mart Former Owner 8/1/2008
U0033695 A1 Food Mart Former Owner 4/1/2006
U0031670 Omega Financial, L.L.C. Former Owner 7/31/2003
U0002119 B Petro Corporation f/k/a Bulk Petroleum Corporation Former Owner 8/15/2000
U0003811 Darco Inc Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Deficiencies (Current)

NOV Number: E0020240955 (Pending)    Issue Date: 4/2/2024    Expiration Date: 6/1/2024    View NOV Form

Tanks Deficiency
Facility Annual Emergency Stop Inspection not completed or inspection report not available.
1, 2, 3 Annual leak detection certification not completed (Required annually).
1, 2, 3 Annual line precision and mechanical line leak detector functional test not completed.
1, 2, 3 Containment support components are cracked, deteriorated or missing. The cover and supporting components that are defective shall be replaced with factory manufactured components. - Containments for STP's are deteriorated and need repair or replacement.
Facility Facility Operation and Maintenance Plan not completed or available.
Facility Financial responsibility must be reported yearly - Expired 3/2/2024
1, 2, 3 Flex connector sacrificial anode system not tested (required every 3 years) - Test anodes and replace as needed
Facility Missing copies of 30 day Walkthrough Inspection Report. - Missing 2023 & 2024
Facility Missing copies of Annual Walkthrough Inspection Report.
Facility Missing copies of current testing certificates for operator training - Clerk at control station had no certicate for operator training.
1, 2, 3 Overfill prevention equipment inspection(s) not completed (Required every 3 years).
1, 2, 3 Shear valve inspection report not completed (Required during Annual Walkthrough Inspection).
1 Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry.
1, 2, 3 Tank monitor does not appear to function properly and requires maintenance. - Printer not functioning without ink.
1, 2, 3 Triennial spill prevention equipment testing not completed.

NOV Number: E0020240960 (Pending)    Issue Date: 4/2/2024    Expiration Date: 6/1/2024    View NOV Form

Tanks Deficiency
Facility Submit Notification Form For Ownership Change - The Notification Form is available at https://webapps.sfm.illinois.gov/USTPortal/NotificationForm. This form is required to be submitted within 30 days of an ownership change.

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 10000 Petroleum Use:
Product: Gasoline - Non Ethanol CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 5/10/1988 Abandoned Material:
Current Age: 36 Abandoned Date:
Install Date: 4/19/1988 Red Tag Issue Date: 4/2/2024
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Sacrificial Anode Flex Connector 11/23/2020 11/23/2023
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 9/20/2022 9/20/2023
Leak Detect - Tank Automatic Tank Gauging EBW Auto-Stik Jr. 2/27/2023 2/27/2024
Overfill Prev Device Overfill Drop Tube Valve 11/19/2020 11/19/2023
Piping Fiberglass Single Wall Piping N/A N/A
Piping Not Installed STP/Tanktop Sump N/A N/A
Spill Contain Device Single Wall Spill Bucket 11/19/2020 11/19/2023
Tank Fiberglass Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Single Wall Piping Precision Test Pass 9/20/2022
Tank Fiberglass Single Wall Precision Test (Tank) Fail 9/20/2022



Tank Number 2

Capacity: 10000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 5/10/1988 Abandoned Material:
Current Age: 36 Abandoned Date:
Install Date: 4/19/1988 Red Tag Issue Date: 4/2/2024
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Sacrificial Anode Flex Connector 11/23/2020 11/23/2023
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 9/20/2022 9/20/2023
Leak Detect - Tank Automatic Tank Gauging EBW Auto-Stik Jr. 2/27/2023 2/27/2024
Overfill Prev Device Overfill Drop Tube Valve 11/19/2020 11/19/2023
Piping Fiberglass Single Wall Piping N/A N/A
Piping Not Installed STP/Tanktop Sump N/A N/A
Spill Contain Device Single Wall Spill Bucket 11/19/2020 11/19/2023
Tank Fiberglass Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Single Wall Piping Precision Test Pass 9/20/2022
Tank Fiberglass Single Wall Precision Test (Tank) Pass 9/20/2022



Tank Number 3

Capacity: 6000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 5/10/1988 Abandoned Material:
Current Age: 36 Abandoned Date:
Install Date: 4/19/1988 Red Tag Issue Date: 4/2/2024
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Sacrificial Anode Flex Connector 11/23/2020 11/23/2023
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 9/20/2022 9/20/2023
Leak Detect - Tank Automatic Tank Gauging EBW Auto-Stik Jr. 2/27/2023 2/27/2024
Overfill Prev Device Overfill Drop Tube Valve 11/19/2020 11/19/2023
Piping Fiberglass Single Wall Piping N/A N/A
Piping Not Installed STP/Tanktop Sump N/A N/A
Spill Contain Device Single Wall Spill Bucket 11/19/2020 11/19/2023
Tank Fiberglass Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Single Wall Piping Precision Test Pass 9/20/2022
Tank Fiberglass Single Wall Precision Test (Tank) Pass 9/20/2022

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Not Installed UDC Sump N/A N/A



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Not Installed UDC Sump N/A N/A



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Not Installed UDC Sump N/A N/A

MFD Motorfuel Dispensing Forms