Notice of Violations (Current)
NOV Number:
E0020251677
(Formal)
Issue Date:
7/3/2025
Expiration Date:
9/1/2025
View NOV Form
| Tanks |
Violations |
| 1, 2 |
Failed to Empty the Tank to 1" or Less - Per 175.810(a)(1), when placing tanks out of service, the tank and lines must be emptied immediately. The USTs are considered empty, when all materials have been removed to one inch or less. Upon my last inspection on 1/29/25, I took stick readings of each tank and both tanks had more than an inch of product (tank #1 - 7 inches & tank #2 - 30.5 inches). Tanks have been red tagged since 7/29/20. |
| 1, 2 |
Remove tank(s) - Single-Walled, Over 30 Years Old and OOS Over One Year - Both tanks are single walled tanks, which were taken out of service on 7/29/20, and are approximately 50 years old. Per 175.810(e) tanks must be removed, as they are now condemned. Here is a link to the licensed UST Decommissioning contractors, that can perform UST tank removals: https://webapps.sfm.illinois.gov/ustsearch/ContractorSearch.aspx |
IEMA Numbers Associated with the Facility
| IEMA Number |
Inspection Date |
Inspection Type |
Permit Number |
| 09-0413 |
4/28/2009 |
Removal Log |
01993-2008REM |
LUST
Fund Eligibility and Deductibility Determinations
| IEMA Number |
Status |
OSFM Received Date |
OSFM Response Date |
Deductible |
Letter |
| 09-0413 |
Eligible |
5/4/2009
|
5/28/2009
|
$10,000
|
|
Tank Number 1
| Capacity: |
10000 |
|
Petroleum Use: |
|
| Product: |
Gasoline |
|
CERCLA Substance: |
|
| Status: |
Condemned Tank |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
5/7/1986 |
|
Abandoned Material: |
|
| Current Age: |
51 |
|
Abandoned Date: |
|
| Install Date: |
5/31/1975 |
|
Red Tag Issue Date: |
7/29/2020 |
| Last Used Date: |
7/29/2020 |
|
Fee Due: |
$0.00 |
| Product Date: |
|
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Impressed Current Cathodic Protection |
9/18/2018 |
9/18/2019 |
|
Corrosion Prot - Tank
|
Impressed Current Cathodic Protection |
9/18/2018 |
9/18/2019 |
|
Leak Detect - Piping
|
Mechanical Pressurized Line Leak Detection |
9/18/2018 |
9/18/2019 |
|
Leak Detect - Tank
|
Automatic Tank Gauging Incon TS 1001 |
No passing test found |
No passing test found |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
No passing test found |
No passing test found |
|
Piping
|
Steel Single Wall Piping |
Not applicable |
Not applicable |
|
Spill Contain Device
|
Single Wall Spill Bucket |
No passing test found |
No passing test found |
|
Tank
|
Steel Single Wall |
Not applicable |
Not applicable |
Additional Tests
No Tests Listed
Tank Number 2
| Capacity: |
4000 |
|
Petroleum Use: |
None |
| Product: |
Diesel Fuel |
|
CERCLA Substance: |
|
| Status: |
Condemned Tank |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
5/7/1986 |
|
Abandoned Material: |
|
| Current Age: |
51 |
|
Abandoned Date: |
|
| Install Date: |
5/31/1975 |
|
Red Tag Issue Date: |
7/29/2020 |
| Last Used Date: |
7/29/2020 |
|
Fee Due: |
$0.00 |
| Product Date: |
|
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Impressed Current Cathodic Protection |
9/18/2018 |
9/18/2019 |
|
Corrosion Prot - Tank
|
Impressed Current Cathodic Protection |
9/18/2018 |
9/18/2019 |
|
Leak Detect - Piping
|
Mechanical Pressurized Line Leak Detection |
9/18/2018 |
9/18/2019 |
|
Leak Detect - Tank
|
Automatic Tank Gauging Incon TS 1001 |
No passing test found |
No passing test found |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
No passing test found |
No passing test found |
|
Piping
|
Steel Single Wall Piping |
Not applicable |
Not applicable |
|
Spill Contain Device
|
Single Wall Spill Bucket |
No passing test found |
No passing test found |
|
Tank
|
Steel Single Wall |
Not applicable |
Not applicable |
Additional Tests
No Tests Listed
Tank Number 3
| Capacity: |
2000 |
|
Petroleum Use: |
|
| Product: |
Gasoline |
|
CERCLA Substance: |
|
| Status: |
Removed |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
4/28/2009 |
|
OSFM
First Notify Date: |
5/7/1986 |
|
Abandoned Material: |
|
| Current Age: |
46 |
|
Abandoned Date: |
|
| Install Date: |
1/1/1963 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
1/1/1963 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Leak Detect - Piping
|
Mechanical Pressurized Line Leak Detection |
No passing test found |
No passing test found |
Additional Tests
No Tests Listed
Tank Number 4
| Capacity: |
560 |
|
Petroleum Use: |
|
| Product: |
Diesel Fuel |
|
CERCLA Substance: |
|
| Status: |
Removed |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
4/28/2009 |
|
OSFM
First Notify Date: |
5/7/1986 |
|
Abandoned Material: |
|
| Current Age: |
48 |
|
Abandoned Date: |
|
| Install Date: |
1/1/1961 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
12/21/1998 |
|
Fee Due: |
$0.00 |
| Product Date: |
1/1/1961 |
|
|
|
Equipment Information
No Equipment Listed
Additional Tests
No Tests Listed
Tank Number 5
| Capacity: |
560 |
|
Petroleum Use: |
|
| Product: |
Diesel Fuel |
|
CERCLA Substance: |
|
| Status: |
Removed |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
4/28/2009 |
|
OSFM
First Notify Date: |
5/7/1986 |
|
Abandoned Material: |
|
| Current Age: |
48 |
|
Abandoned Date: |
|
| Install Date: |
1/1/1961 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
12/21/1998 |
|
Fee Due: |
$0.00 |
| Product Date: |
1/1/1961 |
|
|
|
Equipment Information
No Equipment Listed
Additional Tests
No Tests Listed
Failed test = the latest test has failed.
Not applicable = a test does not apply to this equipment type or configuration.
No passing test found = a passing test is expected but was not found from the source data.
Dispenser Information
Failed test = the latest test has failed.
Not applicable = a test does not apply to this equipment type or configuration.
No passing test found = a passing test is expected but was not found from the source data.
MFD
Motorfuel Dispensing Forms
No Forms Found