| 5, 6 |
Annual leak detection certification not completed (Required annually). - Automatic Tank Gauging EBW Auto-Stik Jr. with SCALD testing expired. |
| 5, 6 |
Line interstitial sensor functional test not accomplished (Required annually). - Sump Sensor testing expired. |
| 5, 6 |
Overfill prevention equipment inspection(s) not completed (Required every 3 years). - Overfill Drop Tube Valve testing expired. |
| 6 |
Tank interstitial sensor functional test not accomplished (Required annually). - Non-Discriminating InterstitialMonitoring Sensors testing expired. |
| 5, 6 |
Triennial spill prevention equipment testing not completed. - Single Wall Spill Bucket testing expired. |
| 5, 6 |
Triennial testing for qualifying piping containment sump not completed (Required every 3 years). - Single Wall STP/Tanktop Sump testing expired. |
| 6 |
Triennial testing for qualifying piping containment sump not completed (Required every 3 years). - Single Wall Transition Sump testing expired. |