Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 3018536
Status: Active
Facility Name: Sunset Marina
Address: 3100 Mississippi River Office
Rock Island, IL 61201
County: Rock Island
Property Parcel:
Facility Type: Marina
Owner Type: Municipal
Green Tag Decal: Z003506
Green Tag Issue Date: 2/27/2024
Green Tag Expiration Date: 12/31/2026

Owner Details

Owner Name: City of Rock Island
Owner Address: 1528 3rd Avenue
Rock Island, IL 61201
Owner Status: Current Owner
Purchase Date:
Type of Financial Responsibility: Self-Insurance
Financial Responsibility Reporting Due Date: 6/28/2025

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Marina 2/27/2024 12/31/2026

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0003038 City of Rock Island Current Owner
U0012937 City of Rock Island Former Owner 6/1/1987

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violations (Current)

No Notice of Violations Found

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 6000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 8/11/1994
OSFM First Notify Date: 4/4/1986 Abandoned Material:
Current Age: 37 Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 2

Capacity: 2000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Exempt Removed Date: 6/1/1987
OSFM First Notify Date: 4/4/1986 Abandoned Material:
Current Age: 37 Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: Fee Due:
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 3

Capacity: 10000 Petroleum Use:
Product: Gasoline - Non Ethanol CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 4/2/1987 Abandoned Material:
Current Age: 38 Abandoned Date:
Install Date: 4/8/1987 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Isolation Boots Flex Connector N/A N/A
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 8/2/2024 8/2/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 450 with CSLD 8/2/2024 8/2/2025
Overfill Prev Device Overfill Drop Tube Valve 7/18/2023 7/18/2026
Piping Fiberglass Double Wall N/A N/A
Piping Flex Connector Steel N/A N/A
Piping Not Installed STP/Tanktop Sump N/A N/A
Piping Single Wall Transition Sump 7/18/2023 7/18/2026
Leak Detect - Piping Sump Sensor 8/2/2024 8/2/2025
Spill Contain Device Single Wall Spill Bucket 7/18/2023 7/18/2026
Tank Fiberglass Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Precision Test (Piping) Pass 8/2/2024
Piping Galvanized Steel Single Wall Piping Precision Test (Piping) Pass 7/18/2023
Piping Transition Sump UDC Sump Franklin Fueling Systems TS-2430 Single Wall Precision Test (Piping) Pass 11/29/2021



Tank Number 4

Capacity: 2000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 4/2/1987 Abandoned Material:
Current Age: 38 Abandoned Date:
Install Date: 4/8/1987 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Isolation Boots Flex Connector N/A N/A
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 8/2/2024 8/2/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 450 with CSLD 8/2/2024 8/2/2025
Overfill Prev Device Overfill Drop Tube Valve 7/18/2023 7/18/2026
Piping Fiberglass Double Wall N/A N/A
Piping Flex Connector Steel N/A N/A
Piping Not Installed STP/Tanktop Sump N/A N/A
Piping Single Wall Transition Sump 7/18/2023 7/18/2026
Leak Detect - Piping Sump Sensor 8/2/2024 8/2/2025
Spill Contain Device Single Wall Spill Bucket 7/18/2023 7/18/2026
Tank Fiberglass Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Precision Test (Piping) Pass 8/2/2024
Piping Galvanized Steel Single Wall Piping Precision Test (Piping) Pass 7/18/2023
Piping Transition Sump UDC Sump Franklin Fueling Systems TS-2430 Single Wall Precision Test (Piping) Pass 11/29/2021

Dispenser Information



Name\ID 1-2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 7/18/2023 7/18/2026
Leak Detect - Piping Sump Sensor 8/2/2024 8/2/2025



Name\ID 3-4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 7/18/2023 7/18/2026
Leak Detect - Piping Sump Sensor 8/2/2024 8/2/2025

MFD Motorfuel Dispensing Forms