Notice of Violatlions (Current)
NOV Number:
E0020251737
(Pending)
Issue Date:
7/9/2025
Expiration Date:
9/7/2025
View NOV Form
Tanks |
Violations |
Facility |
LP gas storage lacks proper collision protection or a 40" measurement from cabinet to a 5" raised sidewalk |
NOV Number:
E0020251738
(Pending)
Issue Date:
7/9/2025
Expiration Date:
9/7/2025
View NOV Form
Tanks |
Violations |
4, 6, 7 |
Containment support components are cracked, deteriorated or missing. The cover and supporting components that are defective shall be replaced with factory manufactured components. - Missing handle on STP ground cover lid |
4, 5, 6, 7 |
Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry. |
NOV Number:
E0020251764
(Pending)
Issue Date:
7/11/2025
Expiration Date:
9/9/2025
View NOV Form
Tanks |
Violations |
Facility |
Miscellaneous - Section 175.210 Attended Self-Service Motor Fuel Dispensing Facilities and Islands
All emergency stops are to be indicated by a sign that reads “EMERGENCY STOP” in at least 2-inch red capital letters. Sign needed at Control Station. |
Facility |
Submit Notification Form for Facility Information Change - https://webapps.sfm.illinois.gov/USTPortal/NotificationForm. Business name has changed. |