Notice of Violatlions (Current)
NOV Number:
E0020251758
(Pending)
Issue Date:
7/10/2025
Expiration Date:
9/8/2025
View NOV Form
Tanks |
Violations |
5 |
Containment support components are cracked, deteriorated or missing. The cover and supporting components that are defective shall be replaced with factory manufactured components. - Spill bucket inner lid needs repair or replacement |
7 |
Containment support components are cracked, deteriorated or missing. The cover and supporting components that are defective shall be replaced with factory manufactured components. - STP inner cover (has large hole) damaged repair or replace |
Facility |
Electrical Does Not Comply - ATG riser has open electrical -wires connected outside of electrical box. |
5, 7 |
Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry. |
NOV Number:
E0020251760
(Pending)
Issue Date:
7/10/2025
Expiration Date:
9/8/2025
View NOV Form
Tanks |
Violations |
Facility |
Fire Extinguishers - 2 4A:60BC extinguishers not provided, 1 at or near control station and 1 in the dispensing areas |
Facility |
Miscellaneous |
Facility |
Miscellaneous - Section 175.210 Attended Self-Service Motor Fuel Dispensing Facilities and Islands
All emergency stops are to be indicated by a sign that reads “EMERGENCY STOP” in at least 2-inch red capital letters. |