Notice of Violations (Current)
NOV Number:
E0020251153
(Pending)
Issue Date:
4/30/2025
Expiration Date:
6/29/2025
View NOV Form
Tanks |
Violation |
5 |
Containment support components are cracked, deteriorated or missing. The cover and supporting components that are defective shall be replaced with factory manufactured components. - Missing handle to ground cover STP |
5, 6, 7 |
Miscellaneous - ATG in alarm; repair/replace as necessary to secure alarm. |
5 |
Open electrical conduit or junction boxes. - Missing plug - open junction box |
5, 6, 7 |
Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry. |
NOV Number:
E0020251175
(Pending)
Issue Date:
5/6/2025
Expiration Date:
7/5/2025
View NOV Form
Tanks |
Violation |
5, 6, 7 |
Line interstitial sensor functional test not accomplished (Required annually). - Dispensers 1/2, 3/4, 5/6 UDC Positive Shut Down Sensors Failed testing |
5, 6, 7 |
Miscellaneous - Leak detector(s) failed annual testing. Repair/replace as necessary. Shall be retested to show passing results. |