Notice of Violatlions (Current)
NOV Number:
E0020252475
(Pending)
Issue Date:
9/22/2025
Expiration Date:
11/21/2025
View NOV Form
| Tanks |
Violations |
| Facility |
Miscellaneous - Section 175.210 Attended Self-Service Motor Fuel Dispensing Facilities and Islands
All emergency stops are to be indicated by a sign that reads “EMERGENCY STOP” in at least 2-inch red capital letters. |
| Facility |
Signs - Dispensers not marked or labeled with the name of product - Dispensers 1/2, 3/4, 5/6, 7/8, - Change to RUL |
NOV Number:
E0020252506
(Pending)
Issue Date:
9/22/2025
Expiration Date:
11/21/2025
View NOV Form
| Tanks |
Violations |
| 6 |
Containment support components are cracked, deteriorated or missing. The cover and supporting components that are defective shall be replaced with factory manufactured components. - STP ground cover must be removable to allow for inspection. |
| 8 |
Containment support components are cracked, deteriorated or missing. The cover and supporting components that are defective shall be replaced with factory manufactured components. - STP ground cover missing handle |
| 10 |
Containment support components are cracked, deteriorated or missing. The cover and supporting components that are defective shall be replaced with factory manufactured components. - STP ground cover missing handle & deteriorated -replace or repair STP ground cover. |
| 10 |
Submit Notification Form for Product Change - No longer selling racing fuel- selling RUL.
Forms can be found at
https://sfm.illinois.gov/about/divisions/petroleum-chemical-safety/applications-and-forms.html |