Division of Petroleum & Chemical Safety

 
Pay Tank Fees Online Print Detail Page Export to Excel

Facility Details

Facility Number: 3001685
Status: Active
Facility Name: JBH Knoxville
Address: 747 Knox County Hwy 10 Knoxville, IL 61448
County: Knox
Property Parcel: 10-20-400-014
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Y001635
Green Tag Issue Date: 1/26/2024
Green Tag Expiration Date: 12/31/2025

Owner Details

Owner Name: JBH Petroleum & Foodmart, Inc.
Owner Address: 747 Knox County Hwy 10 Knoxville, IL 61448
Owner Status: Current Owner / Operator
Purchase Date: 2/19/2015
Type of Financial Responsibility: Designated Savings Account
Financial Responsibility Reporting Due Date: 1/25/2025

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 1/26/2024 12/31/2025

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0037641 JBH Petroleum & Foodmart, Inc. Current Owner / Operator 2/19/2015
U0006232 Growmark, Inc. Former Owner 4/1/1999
U0034572 Alam, Alex Former Owner / Operator 5/1/2007
U0032208 Mangloor, Inc. Former Owner / Operator 3/13/2002

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violatlions (Current)

NOV Number: E0020252025 (Pending)    Issue Date: 8/8/2025    Expiration Date: 10/7/2025    View NOV Form

Tanks Violations
Facility A/B operator retraining required as a result of issuance of the Notice of Violation
Facility Annual Emergency Stop Inspection not completed or inspection report not available.
10 Containment support components are cracked, deteriorated or missing. The cover and supporting components that are defective shall be replaced with factory manufactured components. - Spill bucket lid missing release handle - repair or replace to allow for inspection
Facility Financial responsibility must be reported yearly - Financial Responsibility must be declared annually. The form can be found at https://webapps.sfm.illinois.gov/USTPortal/Forms/FinancialResponsibility
Facility Missing copies of 30 day Walkthrough Inspection Report.
Facility Missing copies of Annual Walkthrough Inspection Report.
Facility Missing copies of current testing certificates for operator training
Facility Missing copy of emergency instructions or emergency procedures plan
Facility Missing list of designated Class A/B & C Operators
10, 11, 12 Monthly line interstitial sensor records not available.
Facility Operations & Maintenance plan missing required frequencies
10, 11, 12 Piping interstitial must be open in all sumps - Dispenser: 7/8S, 8/9S, 9/10
10, 11, 12 Precision tank test required. - A tank precision test is required because of missing passing monthly leak reports.
10, 11, 12 Required monthly tank interstitial sensor records not available. - Missing monthly passing reports for the last ten months.
10, 11, 12 Required monthly tank leak test records not available. - A tank precision test is required because of missing passing monthly leak reports.
10, 11, 12 Shear valve inspection report not completed (Required during Annual Walkthrough Inspection).
10, 11, 12 Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry.
10 Water in containment with required interstitial sensors - Remove water and repair containments to prevent water ingress.

IEMA Numbers Associated with the Facility

IEMA Number Inspection Date Inspection Type Permit Number
15-0818 8/21/2015 Abandonment Log 00855-2015ABN
15-0818 8/20/2015 Removal Log 00752-2015REM
15-0818 8/21/2015 Removal Log 00752-2015REM
17-0793 9/20/2017 Facility Tank Status/Change
17-0793 9/20/2017 Abandonment Log 01111-2017ABN

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
15-0818 Eligible 8/25/2015 9/25/2015 $5,000
20170793 Eligible 2/23/2018 3/2/2018 $5,000 Letter
Pay Tank Fees Online

Tank Information

Tank Number Capacity Product Status Regulated Status Red Tag Issued Fee Due Abandon/Removal Date
1 10000 Diesel Fuel Removed Federal $0.00 08/20/2015 - REM
2 10000 Diesel Fuel Removed Federal $0.00 08/21/2015 - REM
3 10000 Diesel Fuel Abandoned in place Federal $0.00 08/21/2015 - ABN
4 10000 Diesel Fuel Abandoned in place Federal $0.00 08/21/2015 - ABN
5 10000 Gasoline Abandoned in place Federal $0.00 09/20/2017 - ABN
6 10000 Gasoline Abandoned in place Federal $0.00 09/20/2017 - ABN
7 10000 Gasoline Abandoned in place Federal $0.00 09/20/2017 - ABN
8 10000 Gasoline Abandoned in place Federal $0.00 08/21/2015 - ABN
9 560 Heating Oil Removed State $0.00 07/16/1998 - REM
10 12000 Diesel Fuel Currently in use Federal $0.00
11 4000 Gasoline - Premium Currently in use Federal $0.00
12 10000 Gasoline - Regular Currently in use Federal $0.00

Dispenser Information

Name\ID Status
1/2 Active
3/4 Active
5/6 Active
7/8S Active
8/9S Active
9/10 Active

MFD Motorfuel Dispensing Forms