Owner Summary
Click for Facility/Tank Ownership history
| Owner Number |
Owner Name |
Owner Status |
Purchase Date |
| U0014207 |
7-Eleven, Inc. |
Current Owner |
2/15/2010 |
| U0010646 |
Mother Hubbard's Cupboard |
Former Owner |
12/31/1967 |
| U0033923 |
MHC Convenience LLC, Series 1 |
Former Owner / Operator |
11/8/2006 |
| U0035445 |
MHC Realty, LLC |
Former Owner / Operator |
|
| U0022049 |
1000 - 78th W., Inc. |
Former Owner / Operator |
|
Notice of Violations (Current)
No Notice of Violations Found
IEMA Numbers Associated with the Facility
| IEMA Number |
Inspection Date |
Inspection Type |
Permit Number |
| 13-0575 |
5/16/2013 |
Removal Log |
00297-2013REM |
| 13-0575 |
5/17/2013 |
Removal Log |
00297-2013REM |
LUST
Fund Eligibility and Deductibility Determinations
| IEMA Number |
Status |
OSFM Received Date |
OSFM Response Date |
Deductible |
Letter |
| 03-1505 |
Eligible |
3/9/2004
|
3/17/2004
|
$10,000
|
|
Tank Number 1
| Capacity: |
10000 |
|
Petroleum Use: |
|
| Product: |
Diesel Fuel |
|
CERCLA Substance: |
|
| Status: |
Removed |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
5/17/2013 |
|
OSFM
First Notify Date: |
2/26/1986 |
|
Abandoned Material: |
Inert material mixed with portland cement |
| Current Age: |
29 |
|
Abandoned Date: |
12/1/2003 |
| Install Date: |
4/1/1984 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
|
|
|
|
Equipment Information
No Equipment Listed
Additional Tests
No Tests Listed
Tank Number 2
| Capacity: |
10000 |
|
Petroleum Use: |
|
| Product: |
Gasoline |
|
CERCLA Substance: |
|
| Status: |
Removed |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
5/16/2013 |
|
OSFM
First Notify Date: |
2/26/1986 |
|
Abandoned Material: |
|
| Current Age: |
29 |
|
Abandoned Date: |
|
| Install Date: |
4/1/1984 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
|
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Lining Materials Internal |
1/21/2009 |
1/21/2014 |
|
Leak Detect - Piping
|
Mechanical Pressurized Line Leak Detection |
10/31/2012 |
10/31/2013 |
|
Leak Detect - Piping
|
Sump Sensor |
10/31/2012 |
10/31/2013 |
|
Leak Detect - Tank
|
Automatic Tank Gauging Veeder Root TLS 350R with CSLD |
No passing test found |
No passing test found |
|
Overfill Prev Device
|
Ball Float Vent Valve EBW 308 |
No passing test found |
No passing test found |
|
Piping
|
Fiberglass Double Wall |
Not applicable |
Not applicable |
|
Spill Contain Device
|
Single Wall Spill Bucket |
No passing test found |
No passing test found |
|
Tank
|
Steel Single Wall |
Not applicable |
Not applicable |
Additional Tests
| Equipment Type |
Equipment |
Test Type |
Test Result |
Test Date |
|
Leak Detect - Piping
|
Sump Sensor
|
Sensor Functional
|
Pass
|
11/30/2010
|
Tank Number 3
| Capacity: |
10000 |
|
Petroleum Use: |
|
| Product: |
Gasoline |
|
CERCLA Substance: |
|
| Status: |
Removed |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
5/15/2013 |
|
OSFM
First Notify Date: |
2/26/1986 |
|
Abandoned Material: |
|
| Current Age: |
29 |
|
Abandoned Date: |
|
| Install Date: |
4/1/1984 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
|
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Lining Materials Internal |
1/21/2009 |
1/21/2014 |
|
Leak Detect - Piping
|
Mechanical Pressurized Line Leak Detection |
10/31/2012 |
10/31/2013 |
|
Leak Detect - Piping
|
Sump Sensor |
10/31/2012 |
10/31/2013 |
|
Leak Detect - Tank
|
Automatic Tank Gauging Veeder Root TLS 350R with CSLD |
No passing test found |
No passing test found |
|
Overfill Prev Device
|
Ball Float Vent Valve EBW 308 |
No passing test found |
No passing test found |
|
Piping
|
Fiberglass Double Wall |
Not applicable |
Not applicable |
|
Spill Contain Device
|
Single Wall Spill Bucket |
No passing test found |
No passing test found |
|
Tank
|
Steel Single Wall |
Not applicable |
Not applicable |
Additional Tests
| Equipment Type |
Equipment |
Test Type |
Test Result |
Test Date |
|
Leak Detect - Piping
|
Sump Sensor
|
Sensor Functional
|
Pass
|
11/30/2010
|
Tank Number 4
| Capacity: |
6000 |
|
Petroleum Use: |
|
| Product: |
Gasoline |
|
CERCLA Substance: |
|
| Status: |
Removed |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
5/15/2013 |
|
OSFM
First Notify Date: |
9/2/1993 |
|
Abandoned Material: |
|
| Current Age: |
20 |
|
Abandoned Date: |
|
| Install Date: |
8/14/1992 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
9/1/1992 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Jacketed Steel Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Mechanical Pressurized Line Leak Detection |
10/31/2012 |
10/31/2013 |
|
Leak Detect - Piping
|
Sump Sensor |
10/31/2012 |
10/31/2013 |
|
Leak Detect - Tank
|
Automatic Tank Gauging Veeder Root TLS 350R with CSLD |
No passing test found |
No passing test found |
|
Overfill Prev Device
|
Ball Float Vent Valve EBW 308 |
No passing test found |
No passing test found |
|
Piping
|
Fiberglass Double Wall |
Not applicable |
Not applicable |
|
Spill Contain Device
|
Single Wall Spill Bucket |
No passing test found |
No passing test found |
|
Tank
|
Composite Double Wall ACT 100 |
Not applicable |
Not applicable |
Additional Tests
| Equipment Type |
Equipment |
Test Type |
Test Result |
Test Date |
|
Leak Detect - Piping
|
Sump Sensor
|
Sensor Functional
|
Pass
|
11/30/2010
|
Tank Number 5
| Capacity: |
8000 |
|
Petroleum Use: |
|
| Product: |
Bio-Diesel |
|
CERCLA Substance: |
|
| Status: |
Removed |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
5/15/2013 |
|
OSFM
First Notify Date: |
2/17/2004 |
|
Abandoned Material: |
|
| Current Age: |
9 |
|
Abandoned Date: |
|
| Install Date: |
10/22/2003 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
10/22/2003 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Piping
|
Flexible Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Composite Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Mechanical Pressurized Line Leak Detection |
10/31/2012 |
10/31/2013 |
|
Leak Detect - Piping
|
Sump Sensor |
10/31/2012 |
10/31/2013 |
|
Leak Detect - Tank
|
Automatic Tank Gauging Veeder Root TLS 350R with CSLD |
No passing test found |
No passing test found |
|
Overfill Prev Device
|
Ball Float Vent Valve EBW 308 |
No passing test found |
No passing test found |
|
Piping
|
Fiberglass Double Wall |
Not applicable |
Not applicable |
|
Piping
|
Flexible Double Wall A.P.T. Poly Tech |
Not applicable |
Not applicable |
|
Spill Contain Device
|
Single Wall Spill Bucket |
No passing test found |
No passing test found |
|
Tank
|
Composite Double Wall Modern Welding Glasteel II |
Not applicable |
Not applicable |
Additional Tests
| Equipment Type |
Equipment |
Test Type |
Test Result |
Test Date |
|
Leak Detect - Piping
|
Non-Discriminating Sump Sensor
|
Sensor Functional
|
Pass
|
11/30/2010
|
Failed test = the latest test has failed.
Not applicable = a test does not apply to this equipment type or configuration.
No passing test found = a passing test is expected but was not found from the source data.
Dispenser Information
Failed test = the latest test has failed.
Not applicable = a test does not apply to this equipment type or configuration.
No passing test found = a passing test is expected but was not found from the source data.
MFD
Motorfuel Dispensing Forms
No Forms Found