1, 2, 3, 4, 5, 7, 8, 9, 10 |
Line interstitial sensors have been raised and rendered inoperational. - Dispenser 7/8, 9/10,13/14, and 2D/3D |
Facility |
Miscellaneous - Each emergency stop shall be identified by an approved sign on all-weather materials stating "EMERGENCY STOP" in 2 inch red capital letters. Reference 175.210 d)3) (2 Inside behind Counter) |
1, 2, 3, 4, 5, 6, 7, 8, 9, 10 |
Overfill alarm does not appear to function properly. - Light bulb is out. Repair/Replace |
1, 2, 3, 4, 5, 7, 8, 9, 10 |
Piping interstitial must be open in all sumps - (2D/3D, 6D/7D, 8D/9D, 9D, and 19/20) |