Deficiencies (Current)
NOV Number:
E0020241287
(Pending)
Issue Date:
5/6/2024
Expiration Date:
7/5/2024
View NOV Form
Tanks |
Deficiency |
Facility |
Miscellaneous - Cfront center exterior Emergency Shut Off is missing a sign.
175.210 d) 3) Each emergency stop shall be identified by a sign on all-weather materials stating "EMERGENCY
STOP" in 2 inch red capital letters. |
1, 2, 3, 4, 5 |
Piping interstitial must be open in all sumps - 175.420 b) Unless otherwise required by the manufacturer, the dispenser product piping sump jumper tubes shall be removed or the product piping test boots pulled back after testing to allow the interstice to be open to the sump sensors. This is for all sumps. |
5 |
Stick inserted in drop tube overfill device rendering it inoperative - Remove stick. - There is a stick in the E85 drop tube. Remove stick |