Division of Petroleum & Chemical Safety

 
Pay Tank Fees Online Print Detail Page Export to Excel

Facility Details

Facility Number: 2047211
Status: Active
Facility Name: Waterway Gas and Wash
Address: 9208 Skokie Boulevard Skokie, IL 60077
County: Cook
Property Parcel: 10-16-221-007-0000
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Y003276
Green Tag Issue Date: 10/20/2023
Green Tag Expiration Date: 12/31/2025

Owner Details

Owner Name: Waterway Gas and Wash Company
Owner Address: 727 Goddard Avenue Chesterfield, MO 63005
Owner Status: Current Owner
Purchase Date: 6/27/2018
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 2/26/2026

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 10/20/2023 12/31/2025

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0037694 Waterway Gas and Wash Company Current Owner 6/27/2018

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violatlions (Current)

NOV Number: E0020252837 (Pending)    Issue Date: 10/24/2025    Expiration Date: 12/23/2025    View NOV Form

Tanks Violations
Facility Attendant does not have means to remotely monitor or no emergency shutoff switch 20' to 50' from dispenser - Section 175.210g; All dispensing units shall be readily visible from the control station without assistive devices. If view is permanently obstructed, or the dispenser is located so that activity is not readily visible, closed-circuit cameras that provide a view of each side of the dispensing unit and project an image on a screen at least 6 inches in diagonal located at the control station may be used. You may also elect to install an emergency stop switch at least 20 feet but no more than 50 feet from any dispenser with a permanently obstructed view.

NOV Number: E0020252838 (Pending)    Issue Date: 10/24/2025    Expiration Date: 12/23/2025    View NOV Form

Tanks Violations
Facility Annual Emergency Stop Inspection not completed or inspection report not available. - All emergency shutoff switches shall be tested annually to verify they shut down all STPs or dispensers. Perform test, complete form (form is available at www.sfm.illinois.gov) and maintain 2 years on site with other annual testing documentation.
1 Annual leak detection certification not completed (Required annually). - Annual leak detection certification (interstitial sensors/ATG) not completed. Testing shall be completed and submitted to OSFM.
1 Annual leak detection certification not completed (Required annually). - Annual leak detection certification (leak detectors and/or interstitial sensors) not completed. Testing shall be performed.
2 Annual leak detection certification not completed (Required annually). - Annual leak detection certification (interstitial sensors/ATG) not completed. Testing shall be completed and submitted to OSFM.
2 Annual leak detection certification not completed (Required annually). - Annual leak detection certification (leak detectors and/or interstitial sensors) not completed. Testing shall be performed.
3 Annual leak detection certification not completed (Required annually). - Annual leak detection certification (interstitial sensors/ATG) not completed. Testing shall be completed and submitted to OSFM.
3 Annual leak detection certification not completed (Required annually). - Annual leak detection certification (leak detectors and/or interstitial sensors) not completed. Testing shall be performed.
Facility Missing copies of Annual Walkthrough Inspection Report. - Annual Walkthrough by a licensed contractor shall be conducted and 2 years documentation maintained on site.
1, 2, 3 Overfill prevention equipment inspection(s) not completed (Required every 3 years). - Triennial inspection of overfill device (drop tube valve or overfill alarm) has not been completed. Testing shall be completed with passing results and uploaded to OSFM website.
1, 2, 3 Shear valve inspection report not completed (Required during Annual Walkthrough Inspection). - Provide documentation that annual testing of all shear valves has been conducted and passed. Must maintain 2 years of inspection reports.
1, 2, 3 Triennial spill prevention equipment testing not completed. - Triennial inspection/testing of spill bucket(s) has not been completed. Testing shall be completed with passing results uploaded to OSFM.
1, 2, 3 Triennial testing for qualifying piping containment sump not completed (Required every 3 years). - Triennial testing for qualifying STP/dispenser piping containment sump(s) not completed. Testing shall be completed and submitted to OSFM.

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information

Tank Number Capacity Product Status Regulated Status Red Tag Issued Fee Due Abandon/Removal Date
1 20000 Gasoline - Regular Currently in use Federal $0.00
2 12000 Gasoline - Premium Currently in use Federal $0.00
3 8000 Diesel Fuel Currently in use Federal $0.00

Dispenser Information

Name\ID Status
1/2 Active
3/4 Active
5/6 Active
7/8 Active
9/10 Active
11/12 Active

MFD Motorfuel Dispensing Forms

Facility Number Name City Received Date Letter
2047211 Waterway Gas and Wash Skokie 12/02/2021 Letter Form