Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 2047140
Status: Active
Facility Name: OM Wheeling Oil, LLC
Address: 1048 Milwaukee Avenue Wheeling, IL 600903936
County: Cook
Property Parcel: 03-13-200-027-0000
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Y000240
Green Tag Issue Date: 1/24/2024
Green Tag Expiration Date: 12/31/2025

Owner Details

Owner Name: Hutton Wheeling ST, LLC
Owner Address: 736 Cherry Street Chattanooga, TN 37402
Owner Status: Current Owner
Purchase Date: 4/2/2020
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 11/17/2026

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 1/24/2024 12/31/2025

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0040240 Hutton Wheeling ST, LLC Current Owner 4/2/2020
U0039701 OM Group Former Owner 4/6/2020

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violatlions (Current)

NOV Number: E0020252664 (Pending)    Issue Date: 10/7/2025    Expiration Date: 12/6/2025    View NOV Form

Tanks Violations
Facility Annual Emergency Stop Inspection not completed or inspection report not available.
2 Dispensers - hoses cracked, split or worn and require replacement - Diesel hose on dipsenser 13, hose on dispenser 17/18 and 19/20
Facility Missing copies of 30 day Walkthrough Inspection Report. - 30-day Walkthrough Inspection shall be completed, and documentation maintained on site. 30-Day Walkthrough Inspection form available at www.sfm.illinois.gov. The form must be filled out by an A/B Operator, you must, initial each box that applies, date the form each month to ensure it is being done every 30 days, and the A/B operator must print and sign their name at the bottom. If more than one A/B operator fills out the form, then each must print and sign name at the bottom.
Facility Missing copies of Annual Walkthrough Inspection Report.
1, 2, 3, 4 Monthly line interstitial sensor records not available. - Maintain one NORMAL/PASS report per LINE, per month, from ATG.
1, 2, 3, 4 Precision line test required. - Precision line test is required (Per 41 Ill Admin code 175.640(a)(4))
1, 2, 3, 4 Required monthly tank interstitial sensor records not available. - Maintain one NORMAL/PASS report per TANK, per month, from tank monitor.
1, 2, 3, 4 Shear valve inspection report not completed (Required during Annual Walkthrough Inspection).
1, 2, 3, 4 Tank precision test required. - Precision tank test is required due to missing or failed monthly monitoring (Per 41 Ill Admin code 175.630(c)(2))

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 20000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 7/1/2021 Abandoned Material:
Current Age: 5 Abandoned Date:
Install Date: 11/17/2020 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 8/5/2025 8/5/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 450 Plus with CSLD 8/5/2025 8/5/2026
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 8/5/2025 8/5/2026
Overfill Prev Device Overfill Drop Tube Valve 8/27/2024 8/27/2027
Piping Flexible Double Wall Franklin Fueling Systems UPP N/A N/A
Piping Single Wall STP/Tanktop Sump 8/27/2024 8/27/2027
Leak Detect - Piping Sump Sensor with positive shutdown 8/5/2025 8/5/2026
Spill Contain Device Single Wall Spill Bucket 8/27/2024 8/27/2027
Tank Fiberglass Double Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall Franklin Fueling Systems UPP Precision Test (Piping) Pass 6/24/2021
Tank Fiberglass Double Wall XERXES Precision Test (Tank) Pass 6/24/2021



Tank Number 2

Capacity: 20000 Petroleum Use: None
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 7/1/2021 Abandoned Material:
Current Age: 5 Abandoned Date:
Install Date: 11/17/2020 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 8/5/2025 8/5/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 450 Plus with CSLD 8/5/2025 8/5/2026
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 8/5/2025 8/5/2026
Overfill Prev Device Overfill Drop Tube Valve 8/27/2024 8/27/2027
Piping Flexible Double Wall Franklin Fueling Systems UPP N/A N/A
Piping Single Wall STP/Tanktop Sump 8/27/2024 8/27/2027
Leak Detect - Piping Sump Sensor with positive shutdown 8/5/2025 8/5/2026
Spill Contain Device Single Wall Spill Bucket 8/27/2024 8/27/2027
Tank Fiberglass Double Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall Franklin Fueling Systems UPP Precision Test (Piping) Pass 6/24/2021
Tank Fiberglass Double Wall XERXES Precision Test (Tank) Pass 6/24/2021



Tank Number 3

Capacity: 8000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 7/1/2021 Abandoned Material:
Current Age: 5 Abandoned Date:
Install Date: 11/17/2020 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 8/5/2025 8/5/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 450 Plus with CSLD 8/5/2025 8/5/2026
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 8/5/2025 8/5/2026
Overfill Prev Device Overfill Drop Tube Valve 8/27/2024 8/27/2027
Piping Flexible Double Wall Franklin Fueling Systems UPP N/A N/A
Piping Single Wall STP/Tanktop Sump 8/27/2024 8/27/2027
Leak Detect - Piping Sump Sensor with positive shutdown 8/5/2025 8/5/2026
Spill Contain Device Single Wall Spill Bucket 8/27/2024 8/27/2027
Tank Fiberglass Double Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall Franklin Fueling Systems UPP Precision Test (Piping) Pass 6/24/2021
Tank Fiberglass Double Wall XERXES Precision Test (Tank) Pass 6/24/2021



Tank Number 4

Capacity: 12000 Petroleum Use:
Product: E15 CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 7/1/2021 Abandoned Material:
Current Age: 5 Abandoned Date:
Install Date: 11/17/2020 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 8/5/2025 8/5/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 450 Plus with CSLD 8/5/2025 8/5/2026
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 8/5/2025 8/5/2026
Overfill Prev Device Overfill Drop Tube Valve 8/27/2024 8/27/2027
Piping Flexible Double Wall Franklin Fueling Systems UPP N/A N/A
Piping Single Wall STP/Tanktop Sump 8/27/2024 8/27/2027
Leak Detect - Piping Sump Sensor with positive shutdown 8/5/2025 8/5/2026
Spill Contain Device Single Wall Spill Bucket 8/27/2024 8/27/2027
Tank Fiberglass Double Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall Franklin Fueling Systems UPP Precision Test (Piping) Pass 6/24/2021
Tank Fiberglass Double Wall XERXES Precision Test (Tank) Pass 6/24/2021

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 8/27/2024 8/27/2027
Leak Detect - Piping Sump Sensor with positive shutdown 8/5/2025 8/5/2026



Name\ID 11/12

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 8/27/2024 8/27/2027
Leak Detect - Piping Sump Sensor with positive shutdown 8/5/2025 8/5/2026



Name\ID 13/14

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 8/27/2024 8/27/2027
Leak Detect - Piping Sump Sensor with positive shutdown 8/5/2025 8/5/2026



Name\ID 15/16

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 8/27/2024 8/27/2027
Leak Detect - Piping Sump Sensor with positive shutdown 8/5/2025 8/5/2026



Name\ID 17/18

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 8/27/2024 8/27/2027
Leak Detect - Piping Sump Sensor with positive shutdown 8/5/2025 8/5/2026



Name\ID 19/20

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 8/27/2024 8/27/2027
Leak Detect - Piping Sump Sensor with positive shutdown 8/5/2025 8/5/2026



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 8/27/2024 8/27/2027
Leak Detect - Piping Sump Sensor with positive shutdown 8/5/2025 8/5/2026



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 8/27/2024 8/27/2027
Leak Detect - Piping Sump Sensor with positive shutdown 8/5/2025 8/5/2026



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 8/27/2024 8/27/2027
Leak Detect - Piping Sump Sensor with positive shutdown 8/5/2025 8/5/2026



Name\ID 9/10

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 8/27/2024 8/27/2027
Leak Detect - Piping Sump Sensor with positive shutdown 8/5/2025 8/5/2026

MFD Motorfuel Dispensing Forms

Facility Number Name City Received Date Letter
2047140 OM Wheeling Oil, LLC Wheeling 05/17/2021 Letter Form