Notice of Violatlions (Current)
NOV Number:
E0020252428
(Pending)
Issue Date:
9/17/2025
Expiration Date:
11/16/2025
View NOV Form
Tanks |
Violations |
Facility |
Annual Fire Detection Test has not been performed - 2) The fire alarm system shall be installed, tested and maintained according
to NFPA 70 and NFPA 72. The alarm system must also meet the alarm
system requirements of subsections (h)(1)(C) and (h)(2)(D), including the
requirement for an audible alarm when triggered. |
Facility |
Code complying instruction/warning signs are not properly mounted at each dispenser island - Dispenser 11 is missing a warning sign.
Section 175.220 Unattended Self-Service Motor Fuel Dispensing Facilities and Islands
a) Minimum Signage. Signs shall be posted in all-weather materials by each actuator
(or at the dispenser if the actuator is an integral part of the dispenser) and the
lettering shall be not less than ? inch high. The top of the signs shall be mounted
no higher than 10 feet above grade, or at a height approved by OSFM, and shall
include the following wording, at a minimum:
1) "No smoking";
2) "Turn off engine";
3) "Containers for gasoline must be red";
4) "Containers for kerosene must be blue";
5) "It is dangerous and unlawful to fill unapproved containers with gasoline,
diesel or kerosene";
6) "In case of fire or spill use EMERGENCY STOP located at…" (owner
must insert the locations of the emergency stops);
7) "EMERGENCY STOP activation transmits a fire alarm to the fire
department". |
NOV Number:
E0020252429
(Pending)
Issue Date:
9/17/2025
Expiration Date:
11/16/2025
View NOV Form
Tanks |
Violations |
Facility |
Miscellaneous - Emergency shut off sign required at dispenser 11 E Stop.
175.210 d) 3) Equipped with an emergency stop at all control stations, which shall be
conspicuously marked and readily accessible to the attendant, whether or
not the control station is less than 20 feet from any dispenser or a security
booth is provided for the attendant. The emergency stop shall be located
in a position to allow all dispensing devices to be readily visible to the
attendant, or as approved by OSFM. Each emergency stop shall be
identified by a sign on all-weather materials stating "EMERGENCY
STOP" in 2 inch red capital letters. |
1 |
Miscellaneous - Vapor cap is broken. |
3 |
Miscellaneous - Fill cap is broken. |
1, 2, 3, 4 |
Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry. - 175.405 a) 1) A) Spill containment equipment that will prevent release of product to
the environment when the transfer hose is detached from the fill
pipe (e.g., a spill catch basin). Spill containment equipment shall
be maintained in a dry, clean state. |