Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 2047067
Status: Active
Facility Name: 7-Eleven 38544
Address: 6375 N Milwaukee Chicago, IL 60646
County: Cook
Property Parcel: 13-05-100-037-0000
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Z002355
Green Tag Issue Date: 2/14/2024
Green Tag Expiration Date: 12/31/2026

Owner Details

Owner Name: GW Clybourn LLC
Owner Address: 2211 N Elston Ave. Suite 304 Chicago, IL 60614
Owner Status: Current Owner
Purchase Date: 3/20/2018
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 12/13/2025

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 2/14/2024 12/31/2026

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0039615 GW Clybourn LLC Current Owner 3/20/2018

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violatlions (Current)

NOV Number: E0020252014 (Pending)    Issue Date: 8/7/2025    Expiration Date: 10/6/2025    View NOV Form

Tanks Violations
2, 3 Annual leak detection certification not completed (Required annually).
2, 3 Tank interstitial sensor functional test not accomplished (Required annually).
2, 3 Tank interstitial sensors in alarm or failed test, must repair or replace. - Interstitial sensor failed testing by Tanknology on July 29, 2025. Repaired by Anderson Pump on August 5, 2025. Monitor prints out All Functions Normal, but still has Interstitial Alarm on Veeder Root display. Anderson needs to return to site to power down Veeder Root rebooting should clear existing sensor failure.

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 20000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 9/30/2020 Abandoned Material:
Current Age: 5 Abandoned Date:
Install Date: 7/10/2020 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 7/29/2025 7/29/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350R 7/29/2025 7/29/2026
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 7/29/2025 7/29/2026
Overfill Prev Device Overfill Drop Tube Valve 9/12/2023 9/12/2026
Piping Flexible Double Wall OPW Flexworks N/A N/A
Piping Single Wall STP/Tanktop Sump 7/20/2023 7/20/2026
Leak Detect - Piping Sump Sensor with positive shutdown 7/29/2025 7/29/2026
Spill Contain Device Double Wall Spill Bucket 9/12/2023 9/12/2026
Tank Fiberglass Double Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall OPW Flexworks Precision Test (Piping) Pass 7/29/2025
Tank Fiberglass Double Wall XERXES Precision Test (Tank) Pass 10/20/2020



Tank Number 2

Capacity: 8000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 9/30/2020 Abandoned Material:
Current Age: 5 Abandoned Date:
Install Date: 7/10/2020 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 7/29/2025 7/29/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350R 7/29/2025 7/29/2026
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 8/5/2025 8/5/2026
Overfill Prev Device Overfill Drop Tube Valve 11/10/2023 11/10/2026
Piping Flexible Double Wall OPW Flexworks N/A N/A
Piping Single Wall STP/Tanktop Sump 7/20/2023 7/20/2026
Leak Detect - Piping Sump Sensor with positive shutdown 7/29/2025 7/29/2026
Spill Contain Device Double Wall Spill Bucket 11/10/2023 11/10/2026
Tank Fiberglass Double Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall OPW Flexworks Precision Test (Piping) Pass 7/29/2025
Tank Fiberglass Double Wall XERXES Precision Test (Tank) Pass 10/20/2020



Tank Number 3

Capacity: 12000 Petroleum Use: None
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 9/30/2020 Abandoned Material:
Current Age: 5 Abandoned Date:
Install Date: 7/10/2020 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 7/29/2025 7/29/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350R 7/29/2025 7/29/2026
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 8/5/2025 8/5/2026
Overfill Prev Device Overfill Drop Tube Valve 9/12/2023 9/12/2026
Piping Flexible Double Wall OPW Flexworks N/A N/A
Piping Single Wall STP/Tanktop Sump 7/20/2023 7/20/2026
Leak Detect - Piping Sump Sensor with positive shutdown 7/29/2025 7/29/2026
Spill Contain Device Double Wall Spill Bucket 9/12/2023 9/12/2026
Tank Fiberglass Double Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall OPW Flexworks Precision Test (Piping) Pass 7/29/2025
Tank Fiberglass Double Wall XERXES Precision Test (Tank) Pass 10/20/2020

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 7/20/2023 7/20/2026
Leak Detect - Piping Sump Sensor with positive shutdown 7/29/2025 7/29/2026



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 7/20/2023 7/20/2026
Leak Detect - Piping Sump Sensor with positive shutdown 7/29/2025 7/29/2026



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 7/20/2023 7/20/2026
Leak Detect - Piping Sump Sensor with positive shutdown 7/29/2025 7/29/2026



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 7/20/2023 7/20/2026
Leak Detect - Piping Sump Sensor with positive shutdown 7/29/2025 7/29/2026

MFD Motorfuel Dispensing Forms

Facility Number Name City Received Date Letter
2047067 7-Eleven 38544 Chicago 10/14/2020 Letter Form