2, 3 |
Tank interstitial sensors in alarm or failed test, must repair or replace. - Interstitial sensor failed testing by Tanknology on July 29, 2025. Repaired by Anderson Pump on August 5, 2025. Monitor prints out All Functions Normal, but still has Interstitial Alarm on Veeder Root display. Anderson needs to return to site to power down Veeder Root rebooting should clear existing sensor failure. |