Notice of Violatlions (Current)
NOV Number:
E0020261108
(Pending)
Issue Date:
4/23/2026
Expiration Date:
6/22/2026
View NOV Form
| Tanks |
Violations |
| 1, 2 |
Dispensers - the following hoses or breakaways are missing or actively leaking and require immediate replacement (bagged at inspection) - Nozzle holds fuel after use and spills as next user goes to insert in the vehicle. Nozzle bagged and placed out of service. |
| Facility |
Missing copies of current testing certificates for operator training - Copies must be kept on site |
| 1, 2, 3 |
Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry. |
NOV Number:
E0020261109
(Pending)
Issue Date:
4/23/2026
Expiration Date:
6/22/2026
View NOV Form
| Tanks |
Violations |
| Facility |
Attendant does not have means to remotely monitor or no emergency shutoff switch 20' to 50' from dispenser - Unable to see dispensers from control station |
| Facility |
Farthest dispenser is greater than 40' and site lacks a communication system or system is inoperable |