1, 2, 3, 4, 11 |
Containment support components are cracked, deteriorated or missing. The cover and supporting components that are defective shall be replaced with factory manufactured components. - Section 175.410 Submersible, Under-dispenser, Transition and Other Containment Sumps
a) All containment sumps must consist of a factory manufactured containment that is liquid-tight on its sides, bottom and at any penetrations and is compatible with the substance conveyed by the piping. Such containment shall also have a factory manufactured protective cover and supporting components that are properly maintained. If the protective cover or its supporting components are cracked, deteriorated or missing, the cover and supporting components that are defective shall be replaced. SPECIFICALLY, ALL STP HANDLES AT THE MAIN/ATTENDED GAS STATION AND THE E-85 STP HANDLE AT HILLTOP. |
5, 6, 7 |
Line interstitial sensors have been raised and rendered inoperational. - Interstitial sensor has been raised rendering it ineffective. Repair/replace sensor(s) into proper location so that it can function as designed. Specifically at dispenser 23/24. |
5 |
Line leak detection equipment in alarm or failed test, must repair or replace. - Line interstitial sensor(s) in alarm on ATG; Repair/replace sensor(s) as necessary to clear alarm. Specifically Route 12 fuel island "E-85 line not enabled." "E-85 High Line Pressure Alarm" |
6, 8, 10 |
Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry. |
1, 2, 3, 4 |
Water in dispenser containment with interstitial sensors - Remove water and repair containments to prevent water ingress - UDC sumps 11/12 and 23/24 contain liquid, Remove liquid and repair containment to prevent further liquid ingress. |