Dispensers - hoses cracked, split or worn and require replacement - Replace the main hose. |
| 1, 2, 3 |
Line interstitial sensors have been raised and rendered inoperational. - All tanks STP sumps have sensors on top of the manway. All need to be lowered.
175.640 a) 2) All new and existing sump sensors must be installed so as to detect liquid per manufacturer's specifications or, if not specified by the manufacturer, at the lowest point in the sump. |
| 1, 2, 3 |
Piping interstitial must be open in all sumps - 175.420 b) Unless otherwise required by the manufacturer, the dispenser product piping sump jumper tubes shall be removed, or the product piping test boots pulled back after testing to allow the interstice to be open to the sump sensors. This is for all sumps. |