Notice of Violatlions (Current)
NOV Number:
E0020251608
(Pending)
Issue Date:
6/26/2025
Expiration Date:
8/25/2025
View NOV Form
Tanks |
Violations |
1, 2, 3 |
Piping interstitial must be open in all sumps - Remove all jumper tubing/pull back test boots for piping interstitial. 175.420 b. UDC'S 5/6 THROUGH 15/16. |
1, 2, 3 |
Precision tank test required. - Precision tank test is required on tanks if you cannot provide 24 months’ worth of tank “NORMAL” from ATG WITH THE PROPER DATE. |
1, 2, 3 |
Required monthly tank interstitial sensor records not available. - Maintain one NORMAL report per TANK, per month, from ATG. Must maintain 24 months’ worth. THE PRINTED ATG TAPES DO NOT SHOW A PROPER DATE FOR STSS TO VERIFY THE MONTH IT WAS PRINTED. |
NOV Number:
E0020251609
(Pending)
Issue Date:
6/26/2025
Expiration Date:
8/25/2025
View NOV Form
Tanks |
Violations |
Facility |
Attendant does not have means to remotely monitor or no emergency shutoff switch 20' to 50' from dispenser - Section 175.210g; All dispensing units shall be readily visible from the control station without assistive devices. If view is permanently obstructed, or the dispenser is located so that activity is not readily visible, closed-circuit cameras that provide a view of each side of the dispensing unit and project an image on a screen at least 6 inches in diagonal located at the control station may be used. You may also elect to install an emergency stop switch at least 20 feet but no more than 50 feet from any dispenser with a permanently obstructed view. |
Facility |
Farthest dispenser is greater than 40' and site lacks a communication system or system is inoperable - Intercom system not functional; repair/replace as necessary to provide communication at dispensers. |