Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 2046166
Status: Active
Facility Name: Thornton's, Inc. Store #318
Address: 1330 S Neltnor Blvd.
West Chicago, IL 60185
County: Du Page
Property Parcel:
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Y002802
Green Tag Issue Date: 1/26/2024
Green Tag Expiration Date: 12/31/2025

Owner Details

Owner Name: Thorntons, LLC
Owner Address: 2600 James Thornton Way
Louisville, KY 40245
Owner Status: Current Owner
Purchase Date: 2/11/2019
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 2/18/2026

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 8/1/2023 12/31/2025

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0039521 Thorntons, LLC Current Owner 2/11/2019
U0014995 Thornton's, Inc. - DO NOT USE THIS OWNER ID Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violations (Current)

NOV Number: E0020250581 (Pending)    Issue Date: 3/6/2025    Expiration Date: 5/5/2025    View NOV Form

Tanks Violation
Facility Farthest dispenser is greater than 40' and site lacks a communication system or system is inoperable - 175.210 h)The attendant shall at all times be able to communicate with persons in the dispensing area. Repair or replace intercom.

NOV Number: E0020250582 (Pending)    Issue Date: 3/6/2025    Expiration Date: 5/5/2025    View NOV Form

Tanks Violation
Facility Miscellaneous - All emergency shut off switches need new signs. 175.210 d) 3) Equipped with an emergency stop at all control stations, which shall be conspicuously marked and readily accessible to the attendant, whether or not the control station is less than 20 feet from any dispenser or a security booth is provided for the attendant. The emergency stop shall be located in a position to allow all dispensing devices to be readily visible to the attendant, or as approved by OSFM. Each emergency stop shall be identified by a sign on all-weather materials stating "EMERGENCY STOP" in 2 inch red capital letters.
5 Miscellaneous - Tank 5 probe or sensor well needs lid replaced. It is cracked into pieces. A warning cone is on it now.
1, 2, 4, 5 Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry. - Spill and vapor buckets need to be cleaned out. 175.405 a) 1) A) Spill containment equipment that will prevent release of product to the environment when the transfer hose is detached from the fill pipe (e.g., a spill catch basin). Spill containment equipment shall be maintained in a dry, clean state.

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 20000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 5/10/2017 Abandoned Material:
Current Age: 8 Abandoned Date:
Install Date: 9/2/2016 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 3/7/2025 3/7/2026
Leak Detect - Tank Hydrostatic Reservoir Interstitial Monitoring Sensors with monitor 3/7/2025 3/7/2026
Overfill Prev Device Overfill Drop Tube Valve 3/7/2025 3/7/2028
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Single Wall STP/Tanktop Sump 3/13/2023 3/13/2026
Leak Detect - Piping Sump Sensor with positive shutdown 3/7/2025 3/7/2026
Spill Contain Device Double Wall Spill Bucket 3/13/2023 3/13/2026
Tank Fiberglass Brine Filled Double Wall Containment Solutions N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 2

Capacity: 6000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 5/10/2017 Abandoned Material:
Current Age: 8 Abandoned Date:
Install Date: 9/2/2016 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 3/7/2025 3/7/2026
Leak Detect - Tank Hydrostatic Reservoir Interstitial Monitoring Sensors with monitor 3/7/2025 3/7/2026
Overfill Prev Device Overfill Drop Tube Valve 3/7/2025 3/7/2028
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Single Wall STP/Tanktop Sump 3/13/2023 3/13/2026
Leak Detect - Piping Sump Sensor with positive shutdown 3/7/2025 3/7/2026
Spill Contain Device Double Wall Spill Bucket 3/13/2023 3/13/2026
Tank Fiberglass Brine Filled Double Wall Containment Solutions N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 3

Capacity: 6000 Petroleum Use:
Product: E85 CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 5/10/2017 Abandoned Material:
Current Age: 8 Abandoned Date:
Install Date: 9/2/2016 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 3/7/2025 3/7/2026
Leak Detect - Tank Hydrostatic Reservoir Interstitial Monitoring Sensors with monitor 3/7/2025 3/7/2026
Overfill Prev Device Overfill Drop Tube Valve 3/7/2025 3/7/2028
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Single Wall STP/Tanktop Sump 3/13/2023 3/13/2026
Leak Detect - Piping Sump Sensor with positive shutdown 3/7/2025 3/7/2026
Spill Contain Device Double Wall Spill Bucket 3/13/2023 3/13/2026
Tank Fiberglass Brine Filled Double Wall Containment Solutions N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 4

Capacity: 10000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 5/10/2017 Abandoned Material:
Current Age: 8 Abandoned Date:
Install Date: 9/2/2016 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 3/7/2025 3/7/2026
Leak Detect - Tank Hydrostatic Reservoir Interstitial Monitoring Sensors with monitor 3/7/2025 3/7/2026
Overfill Prev Device Overfill Drop Tube Valve 3/7/2025 3/7/2028
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Single Wall STP/Tanktop Sump 3/13/2023 3/13/2026
Leak Detect - Piping Sump Sensor with positive shutdown 3/7/2025 3/7/2026
Spill Contain Device Double Wall Spill Bucket 3/13/2023 3/13/2026
Tank Fiberglass Brine Filled Double Wall Containment Solutions N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 5

Capacity: 20000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 5/10/2017 Abandoned Material:
Current Age: 8 Abandoned Date:
Install Date: 9/2/2016 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 3/7/2025 3/7/2026
Leak Detect - Tank Hydrostatic Reservoir Interstitial Monitoring Sensors with monitor 3/7/2025 3/7/2026
Overfill Prev Device Overfill Alarm 3/7/2025 3/7/2028
Overfill Prev Device Overfill Drop Tube Valve 3/7/2025 3/7/2028
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Single Wall STP/Tanktop Sump 3/13/2023 3/13/2026
Leak Detect - Piping Sump Sensor with positive shutdown 3/7/2025 3/7/2026
Spill Contain Device Double Wall Spill Bucket 3/13/2023 3/13/2026
Tank Fiberglass Brine Filled Double Wall Containment Solutions N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX Precision Test (Piping) Pass 3/7/2025



Tank Number 6

Capacity: 8000 Petroleum Use:
Product: Diesel Exhaust Fluid (Non-Regulated) CERCLA Substance:
Status: Unknown CAS Code:
Regulated Status: Non-Regulated Removed Date:
OSFM First Notify Date: 5/10/2017 Abandoned Material:
Current Age: 8 Abandoned Date:
Install Date: 9/2/2016 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection
Leak Detect - Piping Sump Sensor
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 Plus with CSLD
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors
Overfill Prev Device Overfill Drop Tube Valve
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Spill Contain Device Single Wall Spill Bucket
Tank Fiberglass Double Wall Containment Solutions N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 3/13/2023 3/13/2026
Leak Detect - Piping Sump Sensor with positive shutdown 3/7/2025 3/7/2026



Name\ID 11/12

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 3/13/2023 3/13/2026
Leak Detect - Piping Sump Sensor with positive shutdown 3/7/2025 3/7/2026



Name\ID 13/14

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 3/13/2023 3/13/2026
Leak Detect - Piping Sump Sensor with positive shutdown 3/7/2025 3/7/2026



Name\ID 15/16

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 3/13/2023 3/13/2026
Leak Detect - Piping Sump Sensor with positive shutdown 3/7/2025 3/7/2026



Name\ID 17/18

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 3/13/2023 3/13/2026
Leak Detect - Piping Sump Sensor with positive shutdown 3/7/2025 3/7/2026



Name\ID 19/20

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 3/13/2023 3/13/2026
Leak Detect - Piping Sump Sensor with positive shutdown 3/7/2025 3/7/2026



Name\ID 21

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 3/13/2023 3/13/2026
Leak Detect - Piping Sump Sensor with positive shutdown 3/7/2025 3/7/2026



Name\ID 22

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 3/13/2023 3/13/2026
Leak Detect - Piping Sump Sensor with positive shutdown 3/7/2025 3/7/2026



Name\ID 23

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 3/13/2023 3/13/2026
Leak Detect - Piping Sump Sensor with positive shutdown 3/7/2025 3/7/2026



Name\ID 23 Satellite

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 3/13/2023 3/13/2026
Leak Detect - Piping Sump Sensor with positive shutdown 3/7/2025 3/7/2026



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 3/13/2023 3/13/2026
Leak Detect - Piping Sump Sensor with positive shutdown 3/7/2025 3/7/2026



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 3/13/2023 3/13/2026
Leak Detect - Piping Sump Sensor with positive shutdown 3/7/2025 3/7/2026



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 3/13/2023 3/13/2026
Leak Detect - Piping Sump Sensor with positive shutdown 3/7/2025 3/7/2026



Name\ID 9/10

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 3/13/2023 3/13/2026
Leak Detect - Piping Sump Sensor with positive shutdown 3/7/2025 3/7/2026

MFD Motorfuel Dispensing Forms

Facility Number Name City Received Date Letter
2046166 Thornton's, Inc. Store #318 West Chicago 01/03/2017 Letter Form
2046166 Thornton's, Inc. Store #318 West Chicago 06/10/2016 Letter Form