Notice of Violatlions (Current)
NOV Number:
E0020252685
(Pending)
Issue Date:
10/8/2025
Expiration Date:
12/7/2025
View NOV Form
Tanks |
Violations |
Facility |
Emergency Shutoff Switch required - (Auto Side the farthest dispenser is 173 feet away.)
Emergency shutoff switch shall be installed and located so that at least one emergency shutoff is at least 20 feet but not more than 100 feet from each dispenser. |
2, 3, 4 |
Line interstitial sensors have been raised and rendered inoperational. - UDC's 20S and 21M |
Facility |
Missing copies of 30 day Walkthrough Inspection Report. - (Missing)
30-day Walkthrough Inspection shall be completed, and documentation maintained on site. 30-Day Walkthrough Inspection form available at https://sfm.illinois.gov/content/dam/soi/en/web/sfm/sfmdocuments/documents/30-day-walkthrough-inspection-report.pdf |
1, 2, 3, 4, 5 |
Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry. - Spill Bucket(s) contain(s) liquid and/or debris; remove liquid/debris and maintain clean and dry at all times. |
NOV Number:
E0020252686
(Pending)
Issue Date:
10/8/2025
Expiration Date:
12/7/2025
View NOV Form
Tanks |
Violations |
Facility |
Attendant does not have means to remotely monitor or no emergency shutoff switch 20' to 50' from dispenser - Repair camera system to view all dispensers. |
Facility |
Farthest dispenser is greater than 40' and site lacks a communication system or system is inoperable - Intercom system not functional; repair/replace as necessary to provide communication at dispensers. Reference 175.210 h) |