3, 5 |
Dispensers - hoses cracked, split or worn and require replacement |
1, 2, 3, 4, 5, 6 |
Piping interstitial must be open in all sumps - 175.420 b) Unless otherwise required by the manufacturer, the dispenser product piping sump jumper tubes shall be removed or the product piping test boots pulled back after testing to allow the interstice to be open to the sump sensors. This is for all sumps. |
3, 4, 5, 6 |
Water in containment with required interstitial sensors - Remove water and repair containments to prevent water ingress. - Dispensers 13/14, 15/16, 15 SAT, 16 SAT. Same amount of liquid in bottom of the sumps. Remove liquid. |