Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 2045340
Status: Active
Facility Name: Pilot Travel Center #483
Address: 3801 N. Division Street
Morris, IL 60450
County: Grundy
Property Parcel: 02-27-100-014
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: X003233
Green Tag Issue Date: 10/12/2022
Green Tag Expiration Date: 12/31/2024

Owner Details

Owner Name: Pilot Travel Centers, LLC
Owner Address: 5508 Lonas Rd.
Knoxville, TN 37909
Owner Status: Current Owner
Purchase Date:
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 8/24/2024

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 7/13/2022 12/31/2024

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0011913 Pilot Travel Centers, LLC Current Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Deficiencies (Current)

NOV Number: E0020241217 (Pending)    Issue Date: 4/24/2024    Expiration Date: 6/23/2024    View NOV Form

Tanks Deficiency
Facility Annual Emergency Stop Inspection not completed or inspection report not available. - All emergency shutoff switches shall be tested annually to verify they shut down all STPs or dispensers. Perform test, complete form (form is available at www.sfm.illinois.gov) and maintain on site with other annual testing documentation.
Facility Miscellaneous - All 6 emergency shut off switch signs need to be replaced. They are painted and faded.
Facility Miscellaneous - Warning signs on all auto dispensers need to be replaced. Existing signs are all faded. Be sure the proper signs are installed. If there are any concerns see rules 175.210 O) 1-5.
Facility Missing copies of Annual Walkthrough Inspection Report. - Annual Walkthrough by a licensed contractor shall be conducted and documentation maintained on site.
1, 2, 3, 4, 5, 6 Shear valve inspection report not completed (Required during Annual Walkthrough Inspection). - Provide documentation that annual testing of all shear valves has been conducted and passed.
1, 2, 3, 4, 5, 6 Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry. - Spill Bucket(s) contain(s) liquid and/or debris; remove liquid/debris and maintain clean and dry at all times.

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 16000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 3/2/2015 Abandoned Material:
Current Age: 10 Abandoned Date:
Install Date: 5/23/2014 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 4/25/2024 4/25/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 Plus 4/24/2024 4/24/2025
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 4/24/2024 4/24/2025
Overfill Prev Device Overfill Drop Tube Valve 4/25/2024 4/25/2027
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Single Wall STP/Tanktop Sump 6/7/2023 6/7/2026
Leak Detect - Piping Sump Sensor with positive shutdown 4/25/2024 4/25/2025
Spill Contain Device Double Wall Spill Bucket 5/11/2022 5/11/2025
Tank Fiberglass Double Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX Precision Test Pass 4/24/2024



Tank Number 2

Capacity: 9000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 3/2/2015 Abandoned Material:
Current Age: 10 Abandoned Date:
Install Date: 5/23/2014 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 4/24/2024 4/24/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 Plus 4/24/2024 4/24/2025
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 4/24/2024 4/24/2025
Overfill Prev Device Overfill Drop Tube Valve 4/25/2024 4/25/2027
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Single Wall STP/Tanktop Sump 6/7/2023 6/7/2026
Leak Detect - Piping Sump Sensor with positive shutdown 4/24/2024 4/24/2025
Spill Contain Device Double Wall Spill Bucket 5/11/2022 5/11/2025
Tank Fiberglass Double Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX Precision Test Pass 4/24/2024



Tank Number 3

Capacity: 20000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 3/2/2015 Abandoned Material:
Current Age: 10 Abandoned Date:
Install Date: 5/23/2014 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 4/24/2024 4/24/2025
Leak Detect - Piping Siphon Bar N/A N/A
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 Plus 4/24/2024 4/24/2025
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 4/24/2024 4/24/2025
Overfill Prev Device Overfill Drop Tube Valve 4/25/2024 4/25/2027
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Single Wall STP/Tanktop Sump 6/7/2023 6/7/2026
Leak Detect - Piping Sump Sensor with positive shutdown 4/24/2024 4/24/2025
Spill Contain Device Double Wall Spill Bucket 5/11/2022 5/11/2025
Tank Fiberglass Double Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Leak Detect - Piping Siphon Bar Functional Pass 4/24/2024
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX Precision Test Pass 4/24/2024



Tank Number 4

Capacity: 20000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 3/2/2015 Abandoned Material:
Current Age: 10 Abandoned Date:
Install Date: 5/23/2014 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Siphon Bar N/A N/A
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 Plus 4/24/2024 4/24/2025
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 4/24/2024 4/24/2025
Overfill Prev Device Overfill Drop Tube Valve 4/25/2024 4/25/2027
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Single Wall Transition Sump 6/7/2023 6/7/2026
Leak Detect - Piping Sump Sensor with positive shutdown 4/24/2024 4/24/2025
Spill Contain Device Double Wall Spill Bucket 5/11/2022 5/11/2025
Tank Fiberglass Double Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Leak Detect - Piping Siphon Bar Functional Pass 4/24/2024
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX Precision Test Pass 4/24/2024



Tank Number 5

Capacity: 20000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 3/2/2015 Abandoned Material:
Current Age: 10 Abandoned Date:
Install Date: 5/23/2014 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 4/24/2024 4/24/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 Plus 4/24/2024 4/24/2025
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 4/24/2024 4/24/2025
Overfill Prev Device Overfill Drop Tube Valve 4/25/2024 4/25/2027
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Single Wall STP/Tanktop Sump 6/7/2023 6/7/2026
Leak Detect - Piping Sump Sensor with positive shutdown 4/24/2024 4/24/2025
Spill Contain Device Double Wall Spill Bucket 5/11/2022 5/11/2025
Tank Fiberglass Double Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX Precision Test Pass 4/24/2024



Tank Number 6

Capacity: 20000 Petroleum Use:
Product: B-99 CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 3/2/2015 Abandoned Material:
Current Age: 10 Abandoned Date:
Install Date: 5/23/2014 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Siphon Bar N/A N/A
Leak Detect - Piping European with No Test Req Suction N/A N/A
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 Plus 5/5/2024 5/5/2025
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 5/5/2024 5/5/2025
Overfill Prev Device Overfill Drop Tube Valve 4/25/2024 4/25/2027
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Single Wall STP/Tanktop Sump 6/7/2023 6/7/2026
Leak Detect - Piping Sump Sensor with positive shutdown 5/5/2024 5/5/2025
Piping Single Wall STP/Tanktop Sump 6/7/2023 6/7/2026
Leak Detect - Piping Non-Discriminating Sump Sensor with positive shutdown 6/16/2022 6/16/2023
Spill Contain Device Double Wall Spill Bucket 5/11/2022 5/11/2025
Tank Fiberglass Double Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Leak Detect - Piping Siphon Bar Functional Fail 4/24/2024
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX Precision Test Pass 6/16/2022



Tank Number 7

Capacity: 12000 Petroleum Use:
Product: Diesel Exhaust Fluid (Non-Regulated) CERCLA Substance:
Status: Unknown CAS Code:
Regulated Status: Non-Regulated Removed Date:
OSFM First Notify Date: 3/2/2015 Abandoned Material:
Current Age: 10 Abandoned Date:
Install Date: 5/23/2014 Red Tag Issue Date:
Last Used Date: Fee Due:
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Double Wall UDC Sump 6/7/2023 6/7/2026
Leak Detect - Piping Sump Sensor with positive shutdown 4/24/2024 4/24/2025



Name\ID 11/12

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Double Wall UDC Sump 6/7/2023 6/7/2026
Leak Detect - Piping Sump Sensor with positive shutdown 4/24/2024 4/24/2025



Name\ID 17

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Double Wall UDC Sump 6/7/2023 6/7/2026
Leak Detect - Piping Sump Sensor with positive shutdown 4/24/2024 4/24/2025



Name\ID 18

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Double Wall UDC Sump 6/7/2023 6/7/2026
Leak Detect - Piping Sump Sensor with positive shutdown 4/24/2024 4/24/2025



Name\ID 19

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Double Wall UDC Sump 6/7/2023 6/7/2026
Leak Detect - Piping Sump Sensor with positive shutdown 4/24/2024 4/24/2025



Name\ID 20

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Double Wall UDC Sump 6/7/2023 6/7/2026
Leak Detect - Piping Sump Sensor with positive shutdown 4/24/2024 4/24/2025



Name\ID 21

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Double Wall UDC Sump 6/7/2023 6/7/2026
Leak Detect - Piping Sump Sensor with positive shutdown 4/24/2024 4/24/2025



Name\ID 22

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Double Wall UDC Sump 6/7/2023 6/7/2026
Leak Detect - Piping Sump Sensor with positive shutdown 4/24/2024 4/24/2025



Name\ID 23

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Double Wall UDC Sump 6/7/2023 6/7/2026
Leak Detect - Piping Sump Sensor with positive shutdown 4/24/2024 4/24/2025



Name\ID 24

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Double Wall UDC Sump 6/7/2023 6/7/2026
Leak Detect - Piping Sump Sensor with positive shutdown 4/24/2024 4/24/2025



Name\ID 25

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Double Wall UDC Sump 6/7/2023 6/7/2026
Leak Detect - Piping Sump Sensor with positive shutdown 4/24/2024 4/24/2025



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Double Wall UDC Sump 6/7/2023 6/7/2026
Leak Detect - Piping Sump Sensor with positive shutdown 4/24/2024 4/24/2025



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Double Wall UDC Sump 6/7/2023 6/7/2026
Leak Detect - Piping Sump Sensor with positive shutdown 4/24/2024 4/24/2025



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Double Wall UDC Sump 6/7/2023 6/7/2026
Leak Detect - Piping Sump Sensor with positive shutdown 4/24/2024 4/24/2025



Name\ID 9/10

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Double Wall UDC Sump 6/7/2023 6/7/2026
Leak Detect - Piping Sump Sensor with positive shutdown 4/24/2024 4/24/2025

MFD Motorfuel Dispensing Forms

No Forms Found