Owner Summary
Click for Facility/Tank Ownership history
| Owner Number |
Owner Name |
Owner Status |
Purchase Date |
| U0035671 |
RDK Ventures LLC |
Current Owner |
11/27/2018 |
| U0036614 |
Western Trail Outpost, LLC |
Former Owner |
8/3/2012 |
Notice of Violations (Current)
NOV Number:
E0020261446
(Pending)
Issue Date:
6/4/2026
Expiration Date:
8/3/2026
View NOV Form
| Tanks |
Violations |
| 1, 2, 3 |
Annual leak detection certification not completed (Required annually). - Annual leak detection certification (Interstitial Sensors/ATG) failed testing. Repair/replace as necessary. Retesting shall be completed, and submitted to OSFM via the contractor portal. PER 5/14/2026 TESTING: THE PROBES WOULD NOT GO INTO OVERFILL, HIGH PRODUCT OR MAX PRODUCT. THEREFORE COULD NOT TEST EXTERNAL OVERFILL ALARM. |
IEMA Numbers Associated with the Facility
No IEMA Numbers Found
LUST
Fund Eligibility and Deductibility Determinations
| IEMA Number |
Status |
OSFM Received Date |
OSFM Response Date |
Deductible |
Letter |
| 20161192 |
Eligible |
2/21/2017
|
2/22/2017
|
$5,000
|
Letter
|
Tank Number 1
| Capacity: |
12000 |
|
Petroleum Use: |
|
| Product: |
Gasoline - Regular |
|
CERCLA Substance: |
|
| Status: |
Currently in use |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
12/20/2012 |
|
Abandoned Material: |
|
| Current Age: |
13 |
|
Abandoned Date: |
|
| Install Date: |
10/10/2012 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
12/13/2012 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Flexible Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Electronic Pressurized Line Leak Detection |
5/14/2026 |
5/14/2027 |
|
Leak Detect - Tank
|
Non-Discriminating Interstitial Monitoring Sensors With Monitor |
5/21/2025 |
5/14/2026 |
|
Overfill Prev Device
|
Ball Only Removed Ball Float Vent Valve |
Not applicable |
Not applicable |
|
Overfill Prev Device
|
Overfill Alarm |
6/5/2024 |
6/5/2027 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
6/5/2024 |
6/5/2027 |
|
Piping
|
Flexible Double Wall A.P.T. Poly Tech P150SC |
Not applicable |
Not applicable |
|
Piping
|
Single Wall STP/Tanktop Sump |
8/20/2024 |
8/20/2027 |
Leak Detect - Piping
|
Sump Sensor with positive shutdown |
8/20/2024 |
8/20/2027 |
|
Spill Contain Device
|
Single Wall Spill Bucket |
6/5/2024 |
6/5/2027 |
|
Tank
|
Fiberglass Double Wall XERXES |
Not applicable |
Not applicable |
Additional Tests
| Equipment Type |
Equipment |
Test Type |
Test Result |
Test Date |
|
Piping
|
Flexible Double Wall A.P.T. Poly Tech P150SC
|
Precision Test (Piping)
|
Pass
|
5/14/2026
|
|
Tank
|
Fiberglass Double Wall XERXES
|
Precision Test (Tank)
|
Pass
|
5/14/2019
|
Tank Number 2
| Capacity: |
8000 |
|
Petroleum Use: |
None |
| Product: |
Diesel Fuel |
|
CERCLA Substance: |
|
| Status: |
Currently in use |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
12/20/2012 |
|
Abandoned Material: |
|
| Current Age: |
13 |
|
Abandoned Date: |
|
| Install Date: |
10/10/2012 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
12/13/2012 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Flexible Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Electronic Pressurized Line Leak Detection |
5/14/2026 |
5/14/2027 |
|
Leak Detect - Tank
|
Non-Discriminating Interstitial Monitoring Sensors With Monitor |
5/21/2025 |
5/14/2026 |
|
Overfill Prev Device
|
Ball Only Removed Ball Float Vent Valve |
Not applicable |
Not applicable |
|
Overfill Prev Device
|
Overfill Alarm |
6/5/2024 |
6/5/2027 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
6/5/2024 |
6/5/2027 |
|
Piping
|
Flexible Double Wall A.P.T. Poly Tech P150SC |
Not applicable |
Not applicable |
|
Piping
|
Single Wall STP/Tanktop Sump |
8/20/2024 |
8/20/2027 |
Leak Detect - Piping
|
Sump Sensor with positive shutdown |
8/20/2024 |
8/20/2027 |
|
Spill Contain Device
|
Single Wall Spill Bucket |
6/5/2024 |
6/5/2027 |
|
Tank
|
Fiberglass Double Wall XERXES |
Not applicable |
Not applicable |
Additional Tests
| Equipment Type |
Equipment |
Test Type |
Test Result |
Test Date |
|
Piping
|
Flexible Double Wall A.P.T. Poly Tech P150SC
|
Precision Test (Piping)
|
Pass
|
5/14/2026
|
Tank Number 3
| Capacity: |
4000 |
|
Petroleum Use: |
|
| Product: |
Gasoline - Premium |
|
CERCLA Substance: |
|
| Status: |
Currently in use |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
12/20/2012 |
|
Abandoned Material: |
|
| Current Age: |
13 |
|
Abandoned Date: |
|
| Install Date: |
10/10/2012 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
12/13/2012 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Flexible Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Electronic Pressurized Line Leak Detection |
5/14/2026 |
5/14/2027 |
|
Leak Detect - Tank
|
Non-Discriminating Interstitial Monitoring Sensors With Monitor |
5/21/2025 |
5/14/2026 |
|
Overfill Prev Device
|
Ball Only Removed Ball Float Vent Valve |
Not applicable |
Not applicable |
|
Overfill Prev Device
|
Overfill Alarm |
6/5/2024 |
6/5/2027 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
6/5/2024 |
6/5/2027 |
|
Piping
|
Flexible Double Wall A.P.T. Poly Tech P150SC |
Not applicable |
Not applicable |
|
Piping
|
Single Wall STP/Tanktop Sump |
8/20/2024 |
8/20/2027 |
Leak Detect - Piping
|
Sump Sensor with positive shutdown |
8/20/2024 |
8/20/2027 |
|
Spill Contain Device
|
Single Wall Spill Bucket |
6/5/2024 |
6/5/2027 |
|
Tank
|
Fiberglass Double Wall XERXES |
Not applicable |
Not applicable |
Additional Tests
| Equipment Type |
Equipment |
Test Type |
Test Result |
Test Date |
|
Piping
|
Flexible Double Wall A.P.T. Poly Tech P150SC
|
Precision Test (Piping)
|
Pass
|
5/14/2026
|
Failed test = the latest test has failed.
Not applicable = a test does not apply to this equipment type or configuration.
No passing test found = a passing test is expected but was not found from the source data.
MFD
Motorfuel Dispensing Forms
No Forms Found